12
YORK INTERNATIONAL
DISPLAYING SYSTEM SETPOINTS
The currently programmed Setpoint
values can be
viewed at any time (see page 22) in
SERVICE, LO-
CAL
or
REMOTE
operating mode as follows:
Press and release the appropriate
Setpoint
key
the message will be displayed for 2 seconds.
or
Press and hold the appropriate
Setpoint
key the
message will be displayed as long as the key is
pressed.
or
Press and release the appropriate
Setpoint
key,
then press and release the
DISPLAY HOLD
key.
The message will be displayed until the
DISPLAY
HOLD
key is again pressed and released, or 10
minutes have elapsed, whichever comes first.
To Display
CHILLED LIQUID TEMP
Setpoint:
Use
CHILLED LIQUID TEMP
setpoint key as described
on page 10 to produce the following message:
LEAVING SETPOINT = XX.X °F
NOTE: The value displayed is the actual LCWT set-
point. For example, the value displayed in
LO-
CAL
or
PROGRAM
modes is that which is
operator programmed. The value displayed in
the
REMOTE
mode is that base setpoint with
added temperature reset by an Energy Man-
agement System, via remote LCWT setpoint
(PWM signal) if a remote reset signal was re-
ceived within 30 minutes.
To Display
% CURRENT LIMIT
Setpoint:
Use
% CURRENT LIMIT
setpoint key as described
above to produce the following message:
CURRENT LIMIT = XXX % FLA
NOTE: The value displayed is the actual % current limit
setpoint. For example, the value displayed in
LOCAL
or
PROGRAM
mode is that which is
operator programmed. The value displayed in
the
REMOTE
mode is that which has been pro-
grammed by the Energy Management System
via the remote current limit setpoint input.
If chiller is equipped with a YORK Solid State Starter,
the message is:
CURRENT LIMIT = XXX % FLA; *MTR CUR = 000 FLA
NOTE: On Solid State Starter applications, this value
is programmed at the YORK factory. A special
access code is required.
To Display
PULL DOWN DEMAND
Setpoint:
Use
PULL DOWN DEMAND
setpoint key as described
on page 10 to produce the following message:
SETPOINT = XXX MIN @ XX % FLA XXX MIN LEFT
To Display
CLOCK
Setpoint (Time of Day):
Use
CLOCK
setpoint key as described above to pro-
duce the following message:
TODAY IS DAY XX:XX AM/PM 1/1/92
To Display
DAILY SCHEDULE
Setpoints:
Press and hold the
DAILY SCHEDULE
setpoint key.
The chiller start and stop times for each day of the
week are sequentially displayed, beginning with
Sunday and ending with Holiday. The display will
continuously scroll until the
DAILY SCHEDULE
key
is released.
or
Press and release the
DAILY SCHEDULE
setpoint
key. Then press and release the
DISPLAY HOLD
key. The chiller start and stop times for each day of
the week are sequentially displayed beginning with
Sunday and ending with Holiday. The display will
continuously scroll until the
DISPLAY HOLD
key is
again pressed and released, or 10 minutes have
elapsed, whichever comes first.
The display message for
DAILY SCHEDULE
will scroll
in the following sequence:
SUN START = 08:30 AM STOP = 06:00 PM
MON START = 05:00 AM STOP = 07:00 PM
TUE START = 05:00 AM STOP = 07:00 PM
WED START = 05:00 AM STOP = 07:00 PM
THU START = 05:00 AM STOP = 07:00 PM