810753-UTG-A-0313
Johnson Controls Unitary Products
25
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
RHP13J424S21
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1200
1400
1600
MBH
COP
KW
MBH
COP
KW
MBH
COP
KW
60
60
45.9
4.2
3.23
45.2
4.1
3.20
44.6
4.1
3.18
70
44.7
3.8
3.42
44.5
3.8
3.40
44.4
3.8
3.39
80
43.5
3.5
3.61
43.8
3.6
3.60
44.1
3.6
3.58
47
60
41.8
4.2
2.92
41.5
4.0
3.07
41.2
3.7
3.22
70
40.8
3.9
3.09
40.3
3.7
3.19
39.8
3.5
3.35
80
39.7
3.6
3.27
39.1
3.4
3.35
38.4
3.3
3.43
40
60
39.0
4.0
2.85
38.6
3.8
2.98
38.2
3.6
3.12
70
37.7
3.7
3.00
37.1
3.5
3.13
36.5
3.3
3.25
80
36.3
3.4
3.15
35.5
3.2
3.27
34.8
3.0
3.39
30
60
34.9
3.7
2.73
34.0
3.5
2.85
33.2
3.3
2.97
70
32.6
3.4
2.85
31.7
3.1
2.95
30.8
3.0
3.06
80
30.3
3.0
2.96
29.4
2.8
3.06
28.5
2.6
3.16
17
60
26.6
3.0
2.64
25.8
2.8
2.71
25.0
2.6
2.79
70
22.6
2.6
2.60
21.9
2.4
2.69
21.2
2.2
2.77
80
20.3
2.2
2.67
19.7
2.1
2.77
19.1
1.9
2.87
10
60
20.9
2.5
2.47
20.1
2.3
2.57
19.3
2.1
2.66
70
18.7
2.2
2.50
18.0
2.0
2.60
17.4
1.9
2.70
80
16.4
1.9
2.52
15.9
1.8
2.63
15.4
1.7
2.73
NOTE:
ALL CAPACITIES ARE NET, WITH INDOOR FAN HEAT ALREADY DEDUCTED. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
MBH
COP
KW
–
FC/MC/PC60
1.00
1.00
1.00
–
UC60
1.02
1.03
0.99
RFCX48DE
–
0.98
1.06
0.92
RFCX48DP
–
1.00
0.99
1.01
MX16C
FC60C
0.98
1.06
0.93
MX20D
FC/MC60D
1.00
1.12
0.89
Furnaces
Coils
MBH
COP
KW
R*L*CE16
FC/PC60C
0.98
1.06
0.93
R*L*CE16
UC60C
0.99
1.10
0.90
R*L*CE20
FC/PC60C
1.02
1.11
0.91
R*L*CE20
UC60C
1.02
1.10
0.93
R*9*CE16
FC/PC60C
1.02
1.09
0.93
R*9*CE16
UC60C
1.00
1.07
0.94
R*9*CE20
FC/PC60C
1.02
1.11
0.92
R*9*CE20
UC60C
1.00
1.08
0.93
R*9*DE20
FC/MC/PC60D
1.02
1.12
0.90
R*9*DE20
UC60D
1.00
1.11
0.91