Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. RHP13J244S21
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
600
800
1000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
22.6
25.9
25.9
28.3
29.4
25.2
27.1
26.8
29.2
30.4
27.9
28.3
27.6
30.0
31.4
S.C.
22.6
20.9
18.1
18.1
15.5
25.2
23.9
19.7
19.5
16.1
27.9
26.9
21.3
20.9
16.6
KW
1.60
1.60
1.60
1.70
1.70
1.70
1.70
1.70
1.70
1.70
1.80
1.80
1.80
1.80
1.80
75
T.C.
21.5
24.1
24.2
26.6
28.1
23.9
25.3
25.1
27.5
29.0
26.3
26.4
26.0
28.5
29.9
S.C.
21.5
20.1
17.3
17.3
14.7
23.9
22.8
19.1
18.9
15.4
26.3
25.6
20.9
20.6
16.1
KW
1.70
1.80
1.80
1.80
1.80
1.80
1.90
1.80
1.90
1.90
1.90
1.90
1.90
2.00
2.00
85
T.C.
20.4
22.3
22.4
24.8
26.8
22.6
23.4
23.4
25.9
27.6
24.7
24.5
24.4
26.9
28.4
S.C.
20.4
19.4
16.5
16.4
13.8
22.6
21.8
18.6
18.4
14.7
24.7
24.3
20.6
20.3
15.6
KW
1.90
1.90
1.90
1.90
1.90
2.00
2.00
2.00
2.00
2.00
2.10
2.10
2.10
2.10
2.10
95
T.C.
19.4
20.6
20.6
23.0
25.5
21.2
21.6
21.7
24.2
26.2
23.1
22.6
22.7
25.4
26.9
S.C.
19.4
18.6
15.7
15.6
13.0
21.2
20.8
18.0
17.8
14.0
23.1
22.6
20.2
20.0
15.1
KW
2.00
2.00
2.00
2.00
2.10
2.10
2.10
2.10
2.10
2.20
2.20
2.20
2.20
2.30
2.30
105
T.C.
17.6
18.0
18.0
20.9
23.5
19.4
19.5
18.9
21.9
24.3
21.3
21.0
19.9
23.0
25.1
S.C.
17.6
17.2
14.5
14.7
12.0
19.4
19.3
16.7
16.9
13.2
21.3
21.0
18.8
19.1
14.4
KW
2.10
2.10
2.10
2.20
2.20
2.20
2.20
2.20
2.30
2.30
2.30
2.30
2.30
2.40
2.40
115
T.C.
15.8
15.5
15.4
18.8
21.5
17.6
17.5
16.2
19.7
22.4
19.5
19.5
17.0
20.6
23.3
S.C.
15.8
15.5
13.3
13.9
11.1
17.6
17.5
15.3
16.0
12.4
19.5
19.5
17.0
18.2
13.7
KW
2.20
2.20
2.20
2.30
2.40
2.30
2.30
2.30
2.40
2.50
2.50
2.50
2.40
2.50
2.60
125
T.C.
13.9
13.0
12.7
16.6
19.5
15.8
15.5
13.4
17.4
20.5
17.7
17.9
14.1
18.2
21.5
S.C.
13.9
13.0
12.1
13.0
10.1
15.8
15.5
13.4
15.2
11.5
17.7
17.9
14.1
17.3
13.0
KW
2.30
2.20
2.20
2.40
2.50
2.40
2.40
2.40
2.50
2.60
2.60
2.60
2.50
2.60
2.70
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC32
1.02
1.00
1.02
–
FC/MC/PC35
1.02
1.00
1.02
–
FC/MC/PC37
1.03
1.02
1.02
–
FC/MC/PC43
1.03
1.02
1.02
RFCX24BE
–
1.03
1.02
0.94
RFCX30BE
–
1.03
1.02
0.94
RFCX24BP
–
1.02
0.98
0.98
MX12B
FC/MC35B
1.06
1.03
0.92
MX12B
FC/MC43B
1.02
1.01
0.92
Furnaces
Coils
T.C.
S.C.
KW
R*L*AE12
FC/MC/PC32A
1.05
1.03
0.92
R*L*AE12
FC/MC/PC37A
1.07
1.09
0.92
R*L*BE12
FC/MC/PC35B
1.05
1.06
0.92
R*L*BE12
FC/MC/PC43B
1.07
1.10
0.93
R*L*CE16
FC/MC/PC35C
1.05
1.07
0.92
R*L*CE16
FC/MC/PC43C
1.08
1.10
0.93
R*L*CE20
FC/MC/PC35C
1.07
1.09
0.95
R*L*CE20
FC/MC/PC43C
1.07
1.04
0.93
R*9*AE10
FC/MC/PC32A
1.02
0.99
0.96
R*9*AE10
FC/MC/PC37A
1.02
0.99
0.96
R*9*BE12
FC/MC/PC35B
1.05
1.03
0.92
R*9*BE12
FC/MC/PC43B
1.07
1.05
0.93
R*9*CE16
FC/MC/PC35C
1.05
1.03
0.92
R*9*CE16
FC/MC/PC43C
1.07
1.05
0.92
R*9*CE20
FC/MC/PC35C
1.05
1.03
0.93
R*9*CE20
FC/MC/PC43C
1.07
1.04
0.94