810753-UTG-A-0313
Johnson Controls Unitary Products
19
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. RHP13J484S21
INDOOR COIL MODEL NO.
AHP48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1510
1710
1910
ID DB (°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID WB (°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
47.6
50.1
49.8
54.1
60.7
49.4
50.8
51.0
55.8
61.9
51.2
51.5
52.2
57.5
63.1
S.C.
47.6
44.7
37.8
37.0
30.4
49.4
48.3
39.9
39.3
31.5
51.2
51.5
42.0
41.6
32.6
KW
2.90
2.90
2.90
3.00
3.00
3.00
3.00
3.00
3.00
3.10
3.10
3.10
3.10
3.10
3.20
75
T.C.
45.1
46.6
46.5
50.8
56.9
46.7
47.2
47.5
52.2
58.0
48.4
47.9
48.5
53.6
59.0
S.C.
45.1
43.1
36.2
35.6
28.9
46.7
45.8
38.3
37.8
30.0
48.4
47.9
40.3
40.0
31.1
KW
3.20
3.20
3.20
3.20
3.30
3.20
3.20
3.20
3.30
3.30
3.30
3.30
3.30
3.40
3.40
85
T.C.
42.5
43.1
43.2
47.5
53.2
44.1
43.7
44.0
48.6
54.1
45.6
44.3
44.7
49.7
55.0
S.C.
42.5
41.5
34.7
34.2
27.3
44.1
43.3
36.7
36.2
28.4
45.6
44.3
38.7
38.3
29.6
KW
3.40
3.40
3.40
3.50
3.50
3.50
3.50
3.50
3.50
3.60
3.60
3.60
3.60
3.60
3.70
95
T.C.
40.0
39.6
39.9
44.2
49.4
41.4
40.2
40.4
45.0
50.2
42.8
40.7
41.0
45.8
51.0
S.C.
40.0
39.6
33.1
32.7
25.8
41.4
40.2
35.0
34.7
26.9
42.8
40.7
37.0
36.6
28.0
KW
3.60
3.60
3.60
3.70
3.80
3.70
3.70
3.70
3.80
3.90
3.80
3.80
3.80
3.90
4.00
105
T.C.
37.2
37.1
36.3
40.6
45.3
38.5
37.8
36.8
41.1
45.9
39.7
38.6
37.2
41.7
46.6
S.C.
37.2
37.1
31.6
31.3
24.2
38.5
37.8
33.5
33.2
25.2
39.7
38.6
35.4
35.1
26.3
KW
3.90
3.90
3.90
4.00
4.10
4.00
4.00
3.90
4.00
4.20
4.10
4.10
4.00
4.10
4.20
115
T.C.
34.5
34.5
32.8
36.9
41.1
35.5
35.5
33.1
37.2
41.6
36.6
36.4
33.5
37.6
42.1
S.C.
34.5
34.5
30.0
29.8
22.5
35.5
35.5
31.9
31.7
23.6
36.6
36.4
33.5
33.5
24.6
KW
4.10
4.10
4.10
4.20
4.30
4.20
4.20
4.20
4.30
4.40
4.40
4.40
4.30
4.40
4.50
125
T.C.
31.7
31.9
29.3
33.2
37.0
32.6
33.1
29.5
33.3
37.3
33.5
34.2
29.7
33.4
37.7
S.C.
31.7
31.9
28.5
28.3
20.9
32.6
33.1
29.5
30.1
21.9
33.5
34.2
29.7
31.9
22.9
KW
4.40
4.40
4.30
4.50
4.60
4.50
4.50
4.40
4.50
4.70
4.60
4.60
4.50
4.60
4.80
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC60
0.98
0.97
0.98
–
FC/MC62
0.99
0.98
0.98
–
UC60
0.97
0.95
0.97
RFCX48DE
–
0.99
0.97
0.93
RFCX60DE
–
1.00
0.99
0.92
RFCX48DP
–
0.98
0.95
0.98
RFCX60DP
–
0.98
0.97
0.97
MX16C
FC60C
1.00
0.99
0.92
MX20D
FC/MC60D
1.00
1.00
0.91
MX20D
FC/MC62D
1.01
1.00
0.91
Furnaces
Coils
T.C.
S.C.
KW
R*L*CE16
FC/MC62D
1.00
0.99
0.95
R*L*CE16
FC/PC60C
0.99
0.99
0.94
R*L*CE16
UC60C
0.98
0.96
0.94
R*L*CE20
FC/MC62D
1.00
0.99
0.94
R*L*CE20
FC/PC60C
0.99
0.99
0.94
R*L*CE20
UC60C
1.00
0.97
0.90
R*9*CE16
FC/MC62D
1.00
0.99
0.95
R*9*CE16
FC/PC60C
0.99
0.99
0.95
R*9*CE16
UC60C
0.98
0.96
0.94
R*9*CE20
FC/MC62D
1.00
0.99
0.94
R*9*CE20
FC/PC60C
0.99
0.99
0.94
R*9*CE20
UC60C
0.99
0.96
0.94
R*9*DE20
FC/MC/PC60D
1.00
0.96
0.90
R*9*DE20
FC/MC62D
1.00
0.99
0.95
R*9*DE20
UC60D
0.98
0.95
0.89