![YOKOGAWA YewSeries 80 STED Style S Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/yokogawa/yewseries-80-sted-style-s/yewseries-80-sted-style-s_user-manual_3503932048.webp)
Dec.25, 2019-00
BRAIN Communication Function
Sets each parameter, monitors input/output values, and
adjusts input/output using the JHT200 Handy
Terminal*.
Burnout Function (UP/DOWN/OFF)
Fixed input type: Selection by the jumper switch.
Universal input type: Selection by the parameter.
Calibration
mV DC Input:
Linearity for mV DC and output
Thermocouple Input/RTD Input:
Linearity for temperature and output
Potentiometer Input:
Linearity for resistance value and output
Adjustment Range for Zero and Span
mV DC Input/Thermocouple Input/RTD Input:
±5% of span
Potentiometer Input:
±10% of span
How to Adjust
Fixed input type:
Adjustment by push switch on the front.
Universal input type:
Adjustment using the JHT200 Handy
Terminal*.
*:
When connecting the JHT200 Handy Terminal,
the adapter for modular-jack (model E9786WH)
is required. When using the BT200 BRAIN
Terminal of YOKOGAWA Electric Corporation,
the communication cable of 5-pin connector type
(model F9182EE) and the adapter for modular-
jack (model E9786WH) are required.
n
MOUNTING AND APPEARANCE
Mounting: Indoor rack mounting
Wiring
Signal wiring: ISO M4 size (4mm) screws on
terminal block
Power and Ground wiring
100 V version: JIS C 8303 two-pole plug with
earthing contact (IEC A5-15,
UL458)
Cable length: 300 mm
Power supply terminal type (option
code /TB)
220 V version: CEE 7 VII (CENELEC standard)
plug (option code /A2ER)
Cable length: 300 mm
Power supply terminal type (option
code /A2TB)
External Dimensions:
(Height x Width x Depth from the
mounting face)
180 x 48 x 300 (mm)
Weight: 1.7 kg (including rack-mounting case)
n
STANDARD PERFORMANCE
Accuracy: ±0.5% of span
However, there are the following conditions
for TC and RTD inputs.
<For Thermocouple>
Note that for thermocouple input, add the reference
junction compensation accuracy to the accuracy
above.
Reference Junction Compensation Accuracy
For temperatures 0°C and over:
±0.5°C (except for Types R and S)
±1°C (for Types R and S)
For temperatures below 0°C:
Multiply accuracy for temperatures
over 0°C by K, where
(Thermocouple output change/°C near 0°C)
(Thermocouple output change/°C at measurement temperature)
K =
Reference junction compensation is not performed
for type B.
<For Thermocouple>
±0.5% of span or ±0.1°C, whichever is greater
Burnout Time: 1 minute or less
Maximum Power Consumption
DC voltage: 24 V DC, 75 mA
AC voltage: 100 V AC, 5.5 VA
220 V AC, 7.0 VA
n
POWER SUPPLY AND ISOLATION
Power Supply Rated Voltage:
100 V version:
24-110 VDC , -10 %, +10 %, 100 mA
100-120 VAC , -10 %, +10 %, 50/60 Hz, 8.0 VA
220 V version:
135-300 VDC , -10 %, +10 %, 20 mA
200-240 VAC , -10 %, +10 %, 50/60 Hz, 10.0 VA
Power Supply Input Voltage: AC/DC both usage
100 V version: DC drive 20 to 130 V, no polarity
AC drive 80 to 138 V, 47 to 63 Hz
220 V version: DC drive 120 to 340 V, no polarity
AC drive 138 to 264 V, 47 to 63 Hz
Insulation Resistance
Between I/O terminals and Ground:
100 MΩ/ 500 V DC
Between Power and Ground:
100 MΩ/500 V DC
Dielectric Strength
Between I/O terminals and Ground:
500 V AC for 1 minute.
Between Power and Ground:
1000 V AC for 1 minute (100 V version)
1500 V AC for 1 minute (220 V version)
2