![YOKOGAWA YewSeries 80 STED Style S Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/yokogawa/yewseries-80-sted-style-s/yewseries-80-sted-style-s_user-manual_3503932047.webp)
n
GENERAL
The Model STED Converter accepts a mV DC,
thermocouple, RTD or potentiometer signal, converts
and normalizes it, provides isolation, and outputs 1
to 5 V DC and 4 to 20 mA DC signals. Two types
are prepared for the STED converter: fixed input
type that is fixed to mV DC, thermocouple, RTD
or potentiometer, and universal input type that can
select input type from mV DC, thermocouple or RTD.
Burnout function is provided as standard for each
type.
n
STANDARD SPECIFICATIONS
Input Signals
Input
Signal
Type
mV DC
Input
Thermocouple
Input
(*1)
RTD Input
3-wire
(*2)
Current at
0.2 mA DC
Potentiometer
Input
3-wire
Voltage at
0.5 V DC
Minimum
Span
3 mV
3 mV
10°C
(*3)
80 Ω
Maximum
Span
100 mV
62 mV
650°C
(PT50/Pt100)
500°C (JPt100)
2000 Ω
Max. Zero
Elevation
Whichever is the smaller,
within three times the
span or
Within five
times the span
(temperature)
Up to 50
% of total
resistance
±50 mV
±25 mV
Measuring
Range
See table of Measuring Ranges
shown on the right.
50 % or
more of total
resistance
Measurement
unit
mV
°C, K, °F
°C, K, °F
Ω
Input
Resistance
1 MΩ (Power on)
4 kΩ (Power off)
–
–
Source
(leadwire)
Resistance
Up to 500 Ω
(*4)
No greater than
input span (°C) X
0.4 Ω or 10 Ω per
wire, whichever is
the smaller.
Each leadwire
resistance must
be equal.
(*5)
Maximum 10
Ω per wire
Each leadwire
resistance
must be
equal.
Input
Overload
Up to ± 4 V DC
–
–
*1:
Thermocouple JIS C 1602
、
IEC 60584-1 (ITS-90)
TypeK, T, E, J, R, S, B, N, W3
(Note 1)
, W5
(Note 2)
Note 1: ASTM E988 Standard: W97Re3-W75Re25
(tungsten97% rhenium3%-tungsten75% rhenium25%)
Note 2:ASTM E988 Standard: W95Re5-W74Re26
(tungsten95% rhenium5%-tungsten74% rhenium26%)
*2:
RTD JIS C 1604, IEC 60751 (ITS-90) Pt100
JIS C 1604: 1989, DIN (IPTS-68) Pt100
JIS C 1604: 1989, JPt100
JIS C 1604: 1981, Pt50 JIS C 1604
*3:
When used with BARD-300 or BARD-700, the minimum span
is 30°C (60°C for Pt50). The minimum span for Pt50 is 20°C.
(BARD-300 and BARD-700 are safety barriers of YOKOGAWA.)
*4:
When used with BARD-200 or BARD-600, the internal
resistance of BARD (235 Ω ± 15 Ω) is not included.
(BARD-200 and BARD-600 are safety barriers of YOKOGAWA.)
*5:
When used with BARD-300 or BARD-700, the internal
resistance of BARD (130 Ω ± 3 Ω) is not included.
(BARD-300 and BARD-700 are safety barriers of YOKOGAWA.)
Model STED (Style S)
mV, Temperature and Potentiometer/
Voltage Converter
GS 01B04J01-02E
GS 01B04J01-02E
©Copyright Sep. 2001(MC)
13th Edition Dec. 2019(YK)
For universal input type, select one input type from
mV DC, thermocouple or RTD.
Measuring Ranges for Each Input
Type
Measuring Ranges
mV
–50 to 150 mV
TC
(*1)
Type K
Type T
Type J
Type E
Type B
Type R
Type S
Type N
(*6)
Type W3
(*6)
Type W5
(*6)
–200 to 1200°C
–200 to 350°C
0 to 750°C
–200 to 800°C
600 to 1700°C
0 to 1600°C
0 to 1600°C
–200 to 1200°C
0 to 2000°C
0 to 2000°C
RTD
(*2)
JPt100
Pt50
Pt100 (ITS-90)
Pt100 (IPTS-68)
(*6)
–200 to 510°C
–200 to 649°C
–200 to 850°C
–200 to 660°C
Potentiometer
(*7)
100 to 2000 Ω
(*8)
*6:
For STED-7 type only
*7:
For STED-4 type only
*8:
Total resistance
Output Signals
Output: 1 to 5 V DC (two outputs)
4 to 20 mA DC (one output)
Load Resistance:
2 kΩ or more (1 to 5 V DC output)
750 Ω or less (4 to 20 mA DC output)
General
Specifications
Содержание YewSeries 80 STED Style S
Страница 2: ......
Страница 4: ...Blank...
Страница 10: ...Blank...
Страница 14: ...Blank...
Страница 30: ...Blank...
Страница 40: ...Blank...
Страница 46: ...Blank...