![YOKOGAWA YewSeries 80 STED Style S Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/yokogawa/yewseries-80-sted-style-s/yewseries-80-sted-style-s_user-manual_3503932028.webp)
5-8
IM 01B04J01-02E
5.4 Parameter List
BRAIN communication parameters for STED are as follows.
No.
Symbol
Parameter Name
Setting Range
Unit
Factory-set
Value
Setting Type
01
MODEL
Model Name
Display
––––
Display
02
TAG NO
Tag Number
Display
––––
Display
03
SELF CHK
Self Check
GOOD/ERROR
––––
Display
<Display Parameters>
A
DISPLAY1
Menu Name
A01
INPUT1
Input Display
Display
Note8
Display
A09
OUTPUT1
Output1 Display
Display
%
Display
A10
OUTPUT2
Output2 Display
Display
%
Display
A54
STATUS
Status Display (Note1)
0000 to FFFF
––––
Display
A55
WRT PROTECT
Parameter Write Protect
ON/OFF
––––
OFF
Display
A56
REV NO.
Revision number
Display
––––
Display
A58
MENU REV
Menu Revision number
Display
––––
Display
A60
SELF CHK
Self Check
GOOD/ERROR
––––
Display
B
DISPLAY2
Menu Name
B01
INPUT1
Input Display
Display
Note8
Display
B09
OUTPUT1
Output1 Display
Display
%
Display
B10
OUTPUT2
Output2 Display
Display
%
Display
B60
SELF CHK
Self Check
GOOD/ERROR
––––
Display
<Setting Parameters>
D
SET(I/O)
Menu Name
D01
TAG NO.1
Tag Number1
Up to 8-single-byte
––––
Alphanumeric
D02
TAG NO.2
Tag Number2
Up to 8-single-byte
––––
Alphanumeric
D03
COMMENT1
Comment1
Up to 8-single-byte
––––
Alphanumeric
D04
COMMENT2
Comment2
Up to 8-single-byte
––––
Alphanumeric
D07
SENSOR TYPE1 Sensor Type (Note2)
TC/mV/RTD
––––
(Note16)
Selection
D08
TC TYPE1
TC Type (Note10)
(Note6)
––––
(Note16)
Selection
D09
RTD TYPE1
RTD Type (Note11)
(Note7)
––––
(Note16)
Selection
D13
RESIST1
Resistance (Note3)
1 to 32000
OHM
(Note16)
Real number
D25
UNIT1
Unit (Note4)
degC/K/degF(when
/FCAL is specified.)
––––
(Note16)
Selection
D27
INPUT1 L_RNG
Input Low Range
Depends on the
SENSOR TYPE
Note8
(Note16)
Real Number
D28
INPUT1 H_RNG
Input High Range
Depends on the
SENSOR TYPE
Note8
(Note16)
Real Number
D31
BURN OUT1
Burn Out
OFF/UP/DOWN
––––
(Note17)
Display(Note13)
D33
OUT1 DR
Output1 Direction
DIRECT/REVERSE
––––
DIRECT
Selection
D34
OUT2 DR
Output2 Direction
DIRECT/REVERSE
––––
DIRECT
Selection
D37
RJC
RJC On/Off (Note12)
ON/OFF
––––
ON
Selection(Note14)
D38
RJC CONST
RJC Constant (Note10)
-20.0 to 80.0
Note15
000.0
Real Number
D60
SELF CHK
Self Check
GOOD/ERROR
––––
Display
<Adjustment Parameters>
P
ADJUST
Menu Name
P01
WIRING R1
Wiring Resistance (Note5)
RESET/EXECUTE
––––
RESET
Selecton
P03
ZERO ADJ1
Zero Adjustment (Note5)
Display
Note9
Selection
P04
SPAN ADJ1
Span Adjustment (Note5)
Display
Note9
Selection
P13
OUT1 0%
Output1 0%
-20.00 to 20.00
%
0.00
Real Number
P14
OUT1 100%
Output1 100%
-20.00 to 20.00
%
0.00
Real Number
P15
OUT2 0%
Output2 0%
-20.00 to 20.00
%
0.00
Real Number
P16
OUT2 100%
Output2 100%
-20.00 to 20.00
%
0.00
Real Number
P60
SELF CHK
Self Check
GOOD/ERROR
––––
Display
<Test Parameters>
Q
TEST
Menu Name
Q02
OUT1 TEST
Output1 Test
-25.0 to 125.0
%
0.0
Real Number
Q03
OUT2 TEST
Output2 Test
-25.0 to 125.0
%
0.0
Real Number
Q60
SELF CHK
Self Check
GOOD/ERROR
––––
Display