5-7
IM 01B04J01-02E
Setting
1
2
3
App
1
2
3
5
6
7
8
4
(8) D31: BURN OUT1
Sets the burnout scale for STED-7 type.
The following parameter is initialized if the BURN OUT1 is changed.
P01: WIRING R 1
(9) D33: OUT1 DR and D34: OUT2 DR
Sets the action direction for output 1 and output 2.
If you set REVERSE, outputs 5 V (or 20 mA) for 0% and 1 V (or 4 mA) for 100%.
(10) D37: RJC
Sets available/unavailable of the reference junction temperature compensation-
action for STED-7 type.
(11) D38: RJC CONST (The setting value is available when D37: RJC = OFF)
Can fix the reference junction temperature in the reference junction temperature
compensation-action for STED-7 type.
● Adjustment-related parameters
(1) P01: WIRING R1
Corrects the wiring resistance of input.
(2) P03: ZERO ADJ1
Performs zero adjustment of input.
(3) P04: SPAN ADJ1
Performs span adjustment of input.
(4) P13: OUT1 0% (Note1)
Adjusts 0% of output 1.
(5) P14: OUT1 100% (Note1)
Adjusts 100% of output 1.
(6) P15: OUT2 0% (Note1)
Adjusts 0% of output 2.
(7) P16: OUT2 100% (Note1)
Adjusts 100% of output 2.
● Test-related parameters
(1) Q02: OUT1 TEST (Note1)
Outputs the set value forcibly regardless of input condition.
Q03 has the same function.
Note1: After completing adjustment and test, press the [F4] (OK) key of the Handy Terminal
to return to normal condition (release of forced output).
5.3 Setting of Parameters