7-2
IM 01B04J01-02E
7.1 Action in Fault Condition.
The output condition and error codes (BRAIN communication parameters) in fault condition
are shown in the table below.
• STATUS is displayed in A54 of A:DISPLAY (display), and SELF CHK is displayed in
60 of each item.
• STATUS error code is to be the addition display (hexadecimal number) when two
errors or more occur.
Handy Terminal Display
Output Condition
Description of Error
Remedy
STATUS SELF CHK Error Information
(*1)
Same state as power off
Output: 0% or less
Pushing button
:
Disable
Communication
:
Undefined
Hardware failure
Contact YOKOGAWA's sales
office or sales representative.
Power supply failure,
Fuse broken
0001
ERROR EEPROM ERROR Output: 0% or less
Pushing button: Disable
Communication
:
Undefined
EEPROM error
0002
ERROR EEPROM SUM
ERROR
Output: 0% or less
Pushing button: Disable
Communication
:
Undefined
Parameter error
1000
ERROR AD ERROR
Output: 0% or less
Pushing button: Disable
Communication
:
Normal action
A/D conversion error
0080
ERROR RJC ERROR
Output: (*2)
Pushing button: Enable
Communication
:
Normal action
RJC sensor error
Replace RJC or check
terminal (ambient)
temperature.
0008
ERROR INPUT OVER
RANGE
Output: Normal action
Pushing button: Enable
Communication
:
Normal action
Excessive input, out of
-25 to 125%
Set the input within the range.
(*3)
0010
ERROR RANGE SET
ERROR
Output: Normal action
Pushing button: Enable
Communication
:
Normal action
INPUT1 L_RNG and
INPUT1 H_RNG are
same values.
Set INPUT1 L_RNG or
INPUT1 H_RNG again.
0040
GOOD
None
Output: Normal action
Pushing button: Enable
Communication
:
Normal action
Check power failure
during operation
Write "0000" at the STATUS
display on the Handy
Terminal.
0000
GOOD
None
Output: Normal action
Pushing button: Enable
Communication
:
Normal action
-
-
*1: Displayed when calling
60:
SELF CHK
.
*2: Once you run the unit under a reference junction temperature of -20°C or 80°C, run it per
the burnout settings.
If the burnout setting is UP or DOWN, run the unit such that the input value runs out in
the set direction and outputs according to that input value.
Operation while the burnout setting is OFF results in undefined.
*3: If errors continue even when the input is within the range, the input circuit is broken.