<5. Parameters>
IM 05D01B02-41E
Ref.1.2(1)
Ref.1.1(8)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Remote input type
(INPUT 3 terminals)
Terminals and
Specify the type of remote input as a range code.
See “Instrument Input Range Codes” in the
“2. Initial Settings.”
1 to 5 V (41)
Remote input unit
Select the unit of remote input.
% (0): Percent
F (5): Fahrenheit
C (1): Degree Celsius
- (2): No unit
% (0)
IN3
UNI3
Maximum value
of remote input
range
Set the range of a voltage signal. (RL3 < RH3)
5.000
1.000
RH3
Minimum value of
remote input range
Remote input
decimal point
position
Set the position of the decimal point for remote input.
0 to 4
0: No decimal place, 1: One decimal place,
2 to 4: Two, three, four decimal places
Same as the
PV input decimal
point position
Maximum value
of PV input scale
Minimum value
of PV input scale
RL3
PV unit
Set the unit of PV.
% (0): Percent
F (5): Fahrenheit
C (1): Degree Celsius
- (2): No unit
Same as the
PV input unit
PV decimal point
position
Under normal operation, set the same value as in the PV Input
Decimal Point Position (P.DP1) parameter.
To shift the decimal point for temperature input, use this parameter.
For example, set as “P.DP1 = 0” to change a temperature reading
of one decimal place to that of no decimal places. This involves
reconfiguring the P.RH1 and P.RL1 parameters.
0 to 4
-
P.UN1
P.DP1
Maximum value
of PV range
Under normal operation, keep the values of these parameters
between the maximum and minimum values of the PV input
range.
-19999 to 30000
P.RL1 < P.RH1, where P.RH1-P.RL1
30000
Maximum value
of PV input
range or scale
Minimum value
of PV input
range or scale
P.RH1
Minimum value of
PV range
P.RL1
Max. value of
remote input scale
Set the remote input read-out scale.
-19999 to 30000, where SL3 < SH3
Under normal operation, set the values of these parameters
as shown below.
- When PV input is temperature -
Maximum and minimum values of PV input range
- When PV input is voltage -
Maximum and minimum values of PV input scale
SDP3
SH3
Min. value of
remote input scale
SL3
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
IN2
UNI2
RH2
RL2
SDP2
SH2
SL2
BSL2
RJC2
Remote input
burnout action
selection
Allows the remote input value to be determined as shown
below in case of remote input burnout.
• 105% of remote input scale if set to “Upscale”
• -5.0% of remote input scale if set to “Downscale”
OFF (0): Disable
UP (1): Upscale
DOWN (2): Downscale
OFF (0)
BSL3
21
22
1st Edition : May 31,2000-00