2-14
<Toc>
<2. Initial Settings>
IM 05D01B02-41E
8.
Press the
SET/ENT
key once to display the
parameter “V.AT”.
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/VALV
#1
valve auto tuning
V.AT
=
OFF
9.
Press the
key to display “ON”.
MENU:UTMD/VALV
#1
changing
valve auto tuning
V.AT
=
ON
A/M
DISP
SET/ENT
Blinks during
change.
10.
Press the
SET/ENT
key once. The controller
automatically calibrates the valve position
(fully open or closed).
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/VALV
#1
valve auto tuning
V.AT
=
ON
11.
The controller is viewed as shown below
when the valve position is being automati-
cally calibrated.
MENU:UTMD/VALV
#1
valve auto tuning
V.AT
=
ON
12.
Calibration has ended successfully when
the indication changes from “ON” to
“OFF”.
MENU:UTMD/VALV
#1
valve auto tuning
V.AT
=
OFF
Go to step [14].
13.
Calibration has ended unsuccessfully if the
indication changes from “ON” to “ERR”.
Check the feedback input wiring and carry
out automatic calibration again.
MENU:UTMD/VALV
#1
valve auto tuning
V.AT
=
ERR
14.
Press the
SET/ENT
key for more than 3 seconds.
This returns you to the display shown at
power-on (figure below).
A/M
DISP
SET/ENT
SP :
1.
-10
0
+10
0.0
°
C
DV
1st Edition : May 31,2000-00