<2. Initial Settings>
2-5
IM 05D01B02-41E
1st Edition : May 31,2000-00
8.
Press the
SET/ENT
key once to register the
setpoint.
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/IN
#3
input 1 range high
RH1
=
200.0
9.
Press the
SET/ENT
key once to display the
parameter “RL1” (minimum value of PV
input range).
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/IN
#4
input 1 range low
RL1
=
-270.0
10.
Press the
or
key to display the
required setpoint.
The figure below shows an example of
setting the minimum value of the PV input
range to 0.0
⬚
C.
MENU:UTMD/IN
#4
changing
input 1 range low
RL1
=
0.0
A/M
DISP
SET/ENT
Blinks during
change.
11.
Press the
SET/ENT
key once to register the
setpoint.
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/IN
#4
input 1 range low
RL1
=
0.0
If the type of input is voltage, also config-
ure the PV Input Decimal Point Position
(SDP1), Maximum Value of PV Input Scale
(SH1) and Minimum Value of PV Input Scale
(SL1) parameters that are displayed after
this.
12.
Press the
SET/ENT
key for more than 3 seconds.
This returns you to the display shown at
power-on (figure below).
A/M
DISP
SET/ENT
SP :
1.
-10
0
+10
0.0
°
C
DV