<3. Operations>
3-13
IM 05D01B02-41E
3.9
Manipulating Control Output during Manual
Operation
NOTE
Control output cannot be changed if the controller is stopped. In this case, the preset output
value (operating parameter PO) will be output.
A control output value is linked with a display value changed using the
or
key. Note
that the control output changes as displayed without requiring the
SET/ENT
key.
1.
Bring manual operating display into view. For switching to manual operation, see “3.8 Switching
between AUTO and MAN”.
AL
A/M
PV
REM1
CAS
REM2
MAN1
MAN2
STP
2
4
1
3
PV2
AL
DISP
SET/ENT
0
50
100
1.SP =
100.0
PID:1
OUT =
30.0 %
°
C
MAN1 lamp
ON.
2.
Press the
or
key to change a control output value. You don’t need to press the
SET/ENT
key.
AL
A/M
PV
REM1
CAS
REM2
MAN1
MAN2
STP
2
4
1
3
PV2
AL
DISP
SET/ENT
0
50
100
1.SP =
100.0
PID:1
OUT =
40.0 %
°
C
■
Manipulating the Control Output during Heating/Cooling Control
Showing the Heating/Cooling OUT display.
AL
A/M
PV
REM1
CAS
REM2
MAN1
MAN2
STP
2
4
1
3
PV2
AL
DISP
SET/ENT
1.SP
PID:3
= 100.0
C
= 100.0 %
H = 0.0 %
°
C
CooL
Cooling-side
output
Heating-side
output
Heating/Cooling OUT
display
MAN1 lamp
ON.
1st Edition : May 31,2000-00