■  Parameters to be set

Control Type

Parameter Symbol Name of Parameter

Setting Range

CNT

Control type

PID: PID control

ONOF: ON/OFF control (1 point of hysteresis)

ONOF2: ON/OFF control (2 points of hysteresis)

2P2L: Two-position two-level control

H/C: Heating/cooling control

Note:  Some setpoints may not be displayed depending on the model and suffix codes.

Input Function

Parameter Symbol Name of Parameter

Setting Range

IN

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

UNIT

PV input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit

RH

Maximum value of 

PV input range

Depends on the input type.

- For temperature input -

Set the temperature range that is actually controlled. 

(RL<RH)

- For voltage / current input -

Set the range of a voltage / current signal that is applied.

The scale across which the voltage / current signal is 

actually controlled should be set using the maximum value 

of input scale (SH) and minimum value of input scale (SL).

(Input is always 0% when RL = RH.)

RL

Minimum value of 

PV input range

SDP

PV input scale 

decimal point 

position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

SH

Maximum value of 

PV input scale

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

SL

Minimum value of 

PV input scale

Note 1: SDP, SH, and SL are displayed only for voltage/current input.

Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988

Output Function

Parameter Symbol Name of Parameter

Setting Range

OT

Output type selection

Upper two digits

Lower two digits

Control output or Heating-

side control output (Lower 

two digits)

00: OFF

01: OUT terminals 

      (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals

 

      (voltage pulse)

08: RET/OUT2 terminals

 

      (current)

Cooling-side control output 

(Upper two digits)

00: OFF

01: OUT terminals 

      (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals

 

      (voltage pulse)

08: RET/OUT2 terminals

 

      (current)

CT

Control output cycle 

time

Heating-side control 

output cycle time 

(in Heating/cooling 

control)

0.5 to 1000.0 s

CTc

Cooling-side control 

output cycle time 

(in Heating/cooling 

control)

4.  Adjusting Valve Position Automatically 

 

(for a Position Proportional Type Controller Only)

The following operating procedure describes how to input feedback signals from the 

control valve and adjust the fully-open and fully-closed positions of the control valve 

automatically. The fully-open and fully-closed positions of the valve can be adjusted 

automatically by inputting feedback signals from the valve. To adjust the valve posi-

tion, you need to carry out the connection and bring the controller into manual mode. 

For the connection, see “6. Terminal Wiring Diagrams” in "Installation and Wiring", 

and for the manual mode, see “5. Switching between AUTO and MAN” in "Opera-

tions."

CTL menu is displayed.

 

Press the Right arrow key until OUT menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

 

Press the Up arrow key.

Hold down the keys for 3 seconds.

Show the Operation Display.

OUT menu is displayed.

OFF blinks.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

7.

MAN 

is lit

* When a password is set, PASS is displayed. 

   If the correct password is not entered, setup 

   parameters cannot be changed. 

The parameter V.AT (automatic valve 

position adjustment) is displayed.

ON is displayed.

Blinks during the change. 

  When the adjustment is completed normally, the indication 

  automatically returns to OFF.

●  

When VAT.E appears on PV display, it indicates an error. 

    Check the wiring for feedback input and perform the 

    automatic adjustment again. To perform a valve adjustment 

    manually, see User’s Manual (IM 05P01D31-01EN).

ON has been registered and the automatic 

adjustment of the valve position starts.

V.AT blinks during the automatic adjustment. 

After the adjustment is completed, press 

the DISPLAY key or DISP key once to return 

to the Operation Display.

5.  Setting Alarm Type

The following operating procedure shows an example of changing the alarm-1 type 

(factory default: PV high limit alarm) to PV low limit alarm (setpoint: 02).

MODE menu is displayed.

 

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

Energized/De-energized

Latch action

Stand-by action

The alarm-1 type setpoint 02 (PV low limit)

is registered.

After the setup is completed, press the DISPLAY key 

or DISP key once to return to the Operation Display.

Symbol

● 

To change the alarm type, change the last 2 digits of the 

   5-digit value.

● 

Stand-by action and excitation are turned on or off by 

   selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual (IM 05P01D31-01EN.)

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and 

the Left/Right arrow keys to move between digits. 

MODE menu is displayed.

 

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

Energized/De-energized

Latch action

Stand-by action

The alarm-1 type setpoint 02 (PV low limit)

is registered.

After the setup is completed, press the DISPLAY key 

or DISP key once to return to the Operation Display.

Symbol

● 

To change the alarm type, change the last 2 digits of the 

   5-digit value.

● 

Stand-by action and excitation are turned on or off by 

   selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual (IM 05P01D31-01EN.)

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and 

the Left/Right arrow keys to move between digits. 

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open 

(

unlit

)

Closed 

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open 

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed 

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Cooling-side control output 

high limit (17)

Control output low limit (16)

Cooling-side control output 

low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(un

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See 

User’s

 Manual (IM 05P01D31-01EN).

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open 

(

unlit

)

Closed 

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open 

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed 

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Cooling-side control output 

high limit (17)

Control output low limit (16)

Cooling-side control output 

low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(un

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See 

User’s

 Manual (IM 05P01D31-01EN).

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

6.   Setting Alarm Setpoint

The following operating procedure shows an example of setting the alarm-1 setpoint 

of group 1 to 180.0.

Before setting the alarm setpoint, check the alarm type.

To change the alarm type, see “5. Setting Alarm Type.” 

Press the Right arrow key.

Press the SET/ENTER key.

SP menu is displayed.

Display the parameter and group 

that need to be changed.

Blinks during the change. 

The setpoint has been registered.

After the setup is completed, press 

the DISPLAY key or DISP key once

to return to the Operation Display. 

Press the SET/ENTER key.

Press the Down arrow key until A1 appears.

Press the SET/ENTER key.

Show the Operation Display.
Display MODE menu with the same procedure as described in 

Setting Alarm Type.

1.
2.

3.

4.

5.

6.

Group

The parameter A1 is displayed.

A1 to A4 represent the alarm-1 to -4 setpoints.

Each parameter and group can be changed 

in the Parameter Setting Displays of alarms

using arrow keys.

Up/Down arrow keys: parameters

Left/Right arrow keys: groups

Change the setpoint using the Up/Down arrow 

keys to increase and decrease the value and 

the Left/Right arrow keys to move between digits.

Initializing parameter values

Parameters that you have changed can be initialized to factory default values or user default 

values. For details, see “Parameter Initialization” in the User’s Manual (IM 05P01D31-01EN).

Changing the parameter display levels

This operation guide does not explain all the parameters. To display all the parame-

ters, you need to change the parameter display level to professional setting mode. For 

details, see “Setting Security Functions” in the User’s Manual (IM 05P01D31-01EN).

Содержание UT32A/RSP

Страница 1: ...rman French and Spanish are available for the guide display 2 The LP option can be specified in the combination of Type 2 code any of 0 or 1 and Type 3 code any of 0 or 1 3 The HA option can be specified only when the Type 1 code is 0 or 2 4 When the CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Products with CT option are not intended for EEA ...

Страница 2: ...input for com putation etc Number of inputs See the table of Model and Suffix Codes Input type instrument range and measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrumen...

Страница 3: ...ires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a life span resistance load of 100 000 times use the auxiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay f...

Страница 4: ... Relay contact output NC NO COM Contact rating 250 V AC 3 A 30 V DC 3 A resistance load 111 301 302 303 304 305 306 307 308 309 310 311 312 201 202 203 204 205 206 207 208 210 101 102 103 104 105 106 107 108 109 110 211 212 Current voltage pulse output 0 20 mA DC 4 20 mA DC Voltage pulse 12 V Heating cooling control output Suffix code Type 1 2 Cooling side control output Heating cooling relay cont...

Страница 5: ...ntrol type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the controller to start the Quick setting function This function allows ...

Страница 6: ...RM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY key or DISP key once to return to the Operation Display Symbol To change the alarm type change the last 2 digits of th...

Страница 7: ... User s Manual IM 05P01D31 01EN The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp blinks The OUT symbol appears The output values at 100 0 and 0 appear altern...

Страница 8: ...ystem data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repa...

Страница 9: ...Without Stand by action 0 PV low limit 02 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high limit 12 Target SP deviation low limit 13 Target ...

Страница 10: ...re not described in this manual See User s Manual IM 05P01D31 01EN Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting Range Initial value User setting Display level CNT Control type PID PID control ONOF ON OFF control 1 point of hysteresis ONOF2 ON OFF control 2 points of hysteresis 2P2L Two position two level control H C Heating cooling control PID or H ...

Страница 11: ...cation with checksum LADR Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loop 2 mode P P Peer to peer communication MBRTU EASY BPS Baud rate 600 600 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI ...

Страница 12: ...error status LA ER Ladder error status MCU MCU version DCU DCU version ECU1 ECU 1 version E1 terminal area ECU3 ECU 3 version E3 terminal area ECU4 ECU 4 version E4 terminal area PARA Parameter version H VER Product version SER1 Serial number 1 SER2 Serial number 2 MAC1 MAC address 1 E3 terminal area MAC2 MAC address 2 E3 terminal area MAC3 MAC address 3 E3 terminal area Parameter Display Level Pa...

Отзывы: