background image

IM 05P01D31-81EN  page 2/12

  Mounting the Instrument Main Unit

Provide an instrumented panel steel sheet of 1 to 10 mm thickness.

After opening the mounting hole on the panel, follow the procedures below to install 

the controller:

1)  Insert the controller into the opening from the front of the panel so that the 

terminal board on the rear is at the far side.

2)  Set the brackets in place on the top and bottom of the controller as shown in the figure 

below, then tighten the screws of the brackets. Take care not to overtighten them.

 

Bracket

(top mounting hardware)

Terminal board

Bracket

(bottom mounting hardware)

Panel

Insert a screwdriver into the

brackets to tighten the screws.

Direction to insert the

controller

Appropriate

tightening torque:

0.25 N

m

Insert the controller

into the opening at

the front of the panel.

CAUTION

•  Tighten the screws with appropriate tightening torque within 0.25 N•m. 

Otherwise it may cause the case deformation or the bracket damage.

•  Make sure that foreign materials do not enter the inside of the

  instrument through the case’s slit holes.

  External Dimensions and Panel Cutout Dimensions

(25)

(53) (2.09)

[(N-1)×96+92]

117 (4.61) min.

145 (5.71)

min.

+0.8

0

+0.8

0

92

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N≥5.

65 (2.56)

20  (0.79)

11

(0.43)

UT35A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket

94.6 (3.72)

91.6 (3.61)

105.2 (4.14)

Unit: mm (approx. inch)

96 (3.78)

96 (3.78)

• General mounting

• Side-by-side close mounting

Terminal cover

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.8

0

92

+0.03

0

(3.62        )

(0.98)

+0.03

0

(3.62        )

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×3.78+3.62]         )

+0.03

0

[(N-1)×48+45]

+0.6

0

65 (2.56)

48 (1.89)

11 (0.43)

UT32A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket Terminal cover

94.6 (3.72)

96 (3.78)

105.2 (4.14)

Unit: mm (approx. inch)

70 (2.76)

min.

(25)

145 (5.71)

min.

+0.6

0

45

(53) (2.09)

+0.8

0

92

• General mounting

• Side-by-side close mounting

20  (0.79)

91.6 (3.61)

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N

5.

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.03

0

(3.62        )

+0.02

0

(1.77         ) (0.98)

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×1.89+1.77]        )

+0.02

0

4.  Hardware Specifications

WARNING 

This instrument is for Measurement Category No.1.

Do not use it for measurements in locations falling under Measure-

ment Categories No.2, No.3, and No.4.

Internal Wiring

Outlet

Entrance IV

Cable

III

T

O( I )

II

Category

IEC/EN/CSA

/

UL 

61010-1

EN 61010-2-030

Remarks

No.1

Measurement 

Category I

O (Other)

For measurements performed on circuits not direct

-

ly connected to MAINS.

No.2

Measurement 

Category II

Measurement 

Category II

For measurements performed on circuits directly 

connected to the low-voltage installation.

No.3

Measurement 

Category III

Measurement 

Category III

For measurements performed in the building instal-

lation.

No.4

Measurement 

Category IV

Measurement 

Category IV

For measurements performed at the source of the 

low-voltage installation.

  Input Specifications

●Universal Input (Equipped as standard)

•  Number of inputs: 1

•  Input type, instrument range, and measurement accuracy: See the table below,

Input Type

 Instrument Range

Accuracy

ºC

ºF

Thermo-

couple

K

-270.0 to 1370.0ºC -450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C 

 

±2% of instrument range ±1 digit for 

less than -200.0°C of thermocouple K 

±1% of instrument range ±1 digit for 

less than -200.0°C of thermocouple T

-270.0 to  1000.0ºC -450.0 to 2300.0ºF

-200.0 to  500.0ºC

-200.0 to 1000.0ºF

J

-200.0 to 1200.0ºC -300.0 to 2300.0ºF

T

-270.0 to 400.0ºC

-450.0 to 750.0ºF

0.0 to  400.0ºC

-200.0 to 750.0ºF

B

0.0 to 1800.0ºC

32 to 3300ºF

±0.15% of instrument range ±1 digit 

for 400°C or more

 

±5% of instrument range ±1 digit for 

less than 400°C

S

0.0 to 1700.0ºC

32 to 3100ºF

±0.15% of instrument range ±1 digit 

R

0.0 to 1700.0ºC

32 to 3100ºF

N

-200.0 to 1300.0ºC -300.0 to 2400.0ºF

±0.1% of instrument range ±1 digit

±0.25% of instrument range ±1 digit 

for less than 0°C

E

-270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C

 

±1.5% of instrument range ±1 digit for 

less than -200.0°C of thermocouple E.

L

-200.0 to 900.0ºC

-300.0 to 1600.0ºF

U

-200.0 to 400.0ºC

-300.0 to 750.0ºF

0.0 to 400.0ºC

-200.0 to 1000.0ºF

W

0.0 to 2300.0ºC

32 to 4200ºF

±0.2% of instrument range ±1 digit 

(Note 2)  

Platinel 2

0.0 to 1390.0ºC

32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit  

PR20-40

0.0 to 1900.0ºC

32 to 3400ºF

±0.5% of instrument range ±1 digit for 

800°C or more 

 

Accuracy is not guaranteed for less 

than 800°C.  

W97Re3-

W75Re25

0.0 to 2000.0ºC

32 to 3600ºF

±0.2% of instrument range ±1 digit  

RTD

JPt100

-200.0 to 500.0ºC

-300.0 to 1000.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-150.00 to  150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Pt100

-200.0 to 850.0ºC

-300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-200.0 to 500.0ºC

-300.0 to 1000.0ºF

-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Standard signal

0.400 to 2.000 V

±0.1% of instrument range ±1 digit

1.000 to 5.000 V

DC voltage/current

0.000 to 2.000 V

0.00 to 10.00 V

-10.00 to 20.00 mV

0.0 to 100.0 mV

The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power 

frequency at 50/60 Hz.

Note 

1:  ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range 

 

  between -100 and 200°C.

Note 2:  W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988

• Input sampling (control) period: 200 ms

• Burnout detection:

    Functions at TC, RTD, and standard signal.

    Upscale, downscale, and off can be specified.

  

For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4 mA or less.

• Input bias current: 0.05 µA (for TC or RTD)

• Measured current (RTD): About 0.16 mA

• Input resistance:

    TC or mV input: 1 MΩ or more

    V input: About 1 MΩ

• Allowable signal source resistance:

    TC or mV input: 250 Ω or less

   

Effects of signal source resistance: 0.1 µV/Ω or less

    DC voltage input: 2 kΩ or less

   

Effects of signal source resistance: About 0.01%/100 Ω

•  Allowable wiring resistance:

    RTD input: Max. 150 Ω/wire  (The conductor resistance between the three wires 

 

  shall be equal.)

    Wiring resistance effect: ±0.1ºC/10 Ω

•  Allowable input voltage/current:

    TC, mV and RTD input: ±10 V DC

    V input: ±20 V DC

•  Noise rejection ratio:

    Normal mode: 40 dB or more (at 50/60 Hz)

    Common mode: 120 dB or more (at 50/60 Hz) 

    For 100-240 V AC, the power frequency can be set manually. Automatic

 

  detection is also available.

    For 24 V AC/DC, the power frequency can be set manually.

•  Reference junction compensation error:

    ±1.0ºC (15 to 35ºC), ±1.5ºC (-10 to 15ºC and 35 to 50ºC)

•  Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD

●Remote Input with Direct Input

•  Use: Remote setpoint setting, external compensating input, auxiliary input for com-

putation, etc.

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type, instrument range, and measurement accuracy: See the table below.

Input Type

Instrument Range

Accuracy

Standard signal

0.400 to 2.000 V

±0.2% of instrument range ±1 digit

1.000 to 5.000 V

±0.1% of instrument range ±1 digit

DC voltage

0.000 to 2.000 V

±0.2% of instrument range ±1 digit

0.00 to 10.00 V

±0.1% of instrument range ±1 digit

DC voltage 

for high-input 

impedance

0.000 to 1.250 V

±0.1% of instrument range ±1 digit

•  Input sampling (control) period: Same as universal input

•  Input resistance: About 1 MΩ

  However, 10 MΩ or more for DC voltage for high-input impedance range

•  Burnout detection: Functions at standard signal

  Burnout is determined to have occurred if it is 0.1 V or less.

  Contact Input Specifications

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type: No-voltage contact input or transistor contact input

•  Input contact rating: 12 V DC, 10 mA or more

    Use a contact with a minimum on-current of 1 mA or less.

•  ON/OFF detection:

    No-voltage contact input:

   

Contact resistance of 1 kΩ or less is determined as “ON” and contact

   

resistance of 50 kΩ or more as “OFF.”

    Transistor contact input:

   

Input voltage of 2 V or less is determined as “ON” and leakage current must 

   

not exceed 100 µA when “OFF.”

•  Minimum status detection hold time: Control 50 ms

•  Use: SP switch, operation mode switch, and event input

  Analog Output Specifications

•  Number of outputs:

    Control output: 1

    Cooling-side control output of Heating/cooling type (Retransmission output 

 

  terminal): 1

•  Output type: Current output or voltage pulse output

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

    The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

 

  and power frequency at 50/60 Hz.

•  Voltage pulse output:

    Use: Time proportional output

    On-voltage: 12 V or more/load resistance of 600 Ω or more

    Off-voltage: 0.1 V DC or less

    Time resolution: 10 ms or 0.1% of output, whichever is larger

  Retransmission Output Specifications

•  Number of outputs: Retransmission output; 1, shared with 15 V DC loop power 

supply or Cooling-side control output.

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 Ω or less

•  Current output accuracy (conversion accuracy from PV display on the set scale): 

±0.1% of span (±5% of span for 1 mA or less)

  The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

  and power frequency at 50/60 Hz.

  This is not conversion accuracy through input and output but the performance of 

transmission output itself.

  15 V DC Loop Power Supply Specifications

(Shared with retransmission output or Cooling-side control output.)

•  Power supply: 14.5 to 18.0 V DC

•  Maximum supply current: About 21 mA (with short-circuit current limiting circuit)

  Step Response Time Specifications

Within 1 s (63% of analog output response time when a step change of 10 to 90% of 

input span is applied)

  Relay Contact Output Specifications

•  Contact type and number of outputs:

    Control output: contact point 1c; 1 point

    Heating/cooling type: contact point 1a; 2 points for both heating and cooling sides

    Alarm output: contact point 1a; 3 points (common is independent)

•  Contact rating:

    Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load)

    Contact point 1a (control output): 240 V AC, 3A or 30 V DC, 3A (resistance load)

    Contact point 1a (alarm output): 240 V AC, 1A or 30 V DC, 1 A (resistance load)

•  Use: Time proportional output, alarm output, FAIL output, etc.

•  Time resolution of control output: 10 ms or 0.1% of output, whichever is larger

Note:  The control output should always be used with a load of 10 mA or more.

 

The alarm output should always be used with a load of 1 mA or more.

  Transistor Contact Output Specifications

•  Number of outputs: See the table of Model and Suffix Codes.

•  Output type: Open collector (SINK current)

•  Output contact rating: Max. 24 V DC, 50 mA

•  Output time resolution: Min. 200 ms

•  Use: Alarm output, FAIL output, etc.

  Position Proportional Output Specifications

•  Position signal input:

    Slide resistance: 100 Ω to 2.5 kΩ of total resistance

   

100% side and slide line: with disconnection detection

   

0% side: without disconnection detection

    Current input: 4 to 20 mA (with disconnection detection)

•  Sampling period: 50 ms

•  Measurement resolution: 0.1% of input span

•  Position proportional relay output:

  

UT35A: contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)

  

UT32A: contact point 1a; 2 points, 240 V AC, 3 A or 30 V DC, 3 A (resistance load)

Note: This should always be used with a load of 10 mA or more.

  Heater Break Alarm Specifications

•  Number of inputs: 2

•  Number of outputs: 2 (transistor contact output)

•  Use: Measures the heater current using an external current transformer (CT) and 

generates a heater break alarm when the measured value is less than the break 

detection value.

•  Current transformer input resistance: About 9.4 Ω

• 

Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be applied.)

•  Heater current setting range: OFF, 0.1 to 300.0 Arms

    Heater current measured value display range: 0.0 to 360.0 Arms

 

Note: The CT ratio can be set. CT ratio setting range: 1 to 3300

•  Recommended CT: CT from U.R.D., Ltd.

    CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms

    CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms

•  Heater current measurement period: 200 ms

•  Heater current measurement accuracy: ±5% of current transformer input range 

span ± 1digit (CT error is not included.)

• 

Heater current detection resolution: Within 1/250 of current transformer input range span

•  Break detection On-time: Min. 0.2 second (for time proportional output)

  24 V DC Loop Power Supply Specifications

•  Use: Power is supplied to a 2-wire transmitter.

•  Power supply: 21.6 to 28.0 V DC

•  Rated current: 4 to 20 mA DC

•  Maximum supply current: About 30 mA (with short-circuit current limiting circuit.)

■  Safety and EMC Standards

•  Safety: 

  Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-2-201 (CE), IEC/EN 61010-

2-030 (CE), approved by CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL 

61010-1.

  Installation category: II

  Pollution degree: 2

  Measurement category: I (CAT I) (UL, CSA)

  

 

    

O (Other) (CE)

  Rated measurement input voltage: Max. 10 V DC

  Rated transient overvoltage: 1500 V (*)

 

* This is a reference safety standard value for measurement category I of CSA/UL 61010-

1, and for measurement category O of IEC/EN 61010-2-030. This value is not necessarily a 

guarantee of instrument performance.

•  EMC standards:

 

Compliant with CE marking

 

EN 61326-1 Class A, Table 2 (For use in industrial locations),

 

EN 61326-2-3

 

* The instrument continues to operate at a measurement accuracy of within ±20% of the 

range during testing.

 

EN 55011 Class A, Group 1

 

EN 61000-3-2 Class A

 

EN 61000-3-3

 

EMC Regulatory Arrangement in Australia and New Zealand (for all model includ-

ing LL50A)

 

EN 55011 Class A, Group 1

•  KC marking:

 

Electromagnetic wave interference prevention standard, electromagnetic wave 

protection standard compliance.

Содержание UT32A/RSP

Страница 1: ...rman French and Spanish are available for the guide display 2 The LP option can be specified in the combination of Type 2 code any of 0 or 1 and Type 3 code any of 0 or 1 3 The HA option can be specified only when the Type 1 code is 0 or 2 4 When the CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Products with CT option are not intended for EEA ...

Страница 2: ...input for com putation etc Number of inputs See the table of Model and Suffix Codes Input type instrument range and measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrumen...

Страница 3: ...ires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a life span resistance load of 100 000 times use the auxiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay f...

Страница 4: ... Relay contact output NC NO COM Contact rating 250 V AC 3 A 30 V DC 3 A resistance load 111 301 302 303 304 305 306 307 308 309 310 311 312 201 202 203 204 205 206 207 208 210 101 102 103 104 105 106 107 108 109 110 211 212 Current voltage pulse output 0 20 mA DC 4 20 mA DC Voltage pulse 12 V Heating cooling control output Suffix code Type 1 2 Cooling side control output Heating cooling relay cont...

Страница 5: ...ntrol type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the controller to start the Quick setting function This function allows ...

Страница 6: ...RM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY key or DISP key once to return to the Operation Display Symbol To change the alarm type change the last 2 digits of th...

Страница 7: ... User s Manual IM 05P01D31 01EN The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp blinks The OUT symbol appears The output values at 100 0 and 0 appear altern...

Страница 8: ...ystem data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repa...

Страница 9: ...Without Stand by action 0 PV low limit 02 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high limit 12 Target SP deviation low limit 13 Target ...

Страница 10: ...re not described in this manual See User s Manual IM 05P01D31 01EN Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting Range Initial value User setting Display level CNT Control type PID PID control ONOF ON OFF control 1 point of hysteresis ONOF2 ON OFF control 2 points of hysteresis 2P2L Two position two level control H C Heating cooling control PID or H ...

Страница 11: ...cation with checksum LADR Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loop 2 mode P P Peer to peer communication MBRTU EASY BPS Baud rate 600 600 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI ...

Страница 12: ...error status LA ER Ladder error status MCU MCU version DCU DCU version ECU1 ECU 1 version E1 terminal area ECU3 ECU 3 version E3 terminal area ECU4 ECU 4 version E4 terminal area PARA Parameter version H VER Product version SER1 Serial number 1 SER2 Serial number 2 MAC1 MAC address 1 E3 terminal area MAC2 MAC address 2 E3 terminal area MAC3 MAC address 3 E3 terminal area Parameter Display Level Pa...

Отзывы: