IM 05P01D31-81EN page 2/12
■
Mounting the Instrument Main Unit
Provide an instrumented panel steel sheet of 1 to 10 mm thickness.
After opening the mounting hole on the panel, follow the procedures below to install
the controller:
1) Insert the controller into the opening from the front of the panel so that the
terminal board on the rear is at the far side.
2) Set the brackets in place on the top and bottom of the controller as shown in the figure
below, then tighten the screws of the brackets. Take care not to overtighten them.
Bracket
(top mounting hardware)
Terminal board
Bracket
(bottom mounting hardware)
Panel
Insert a screwdriver into the
brackets to tighten the screws.
Direction to insert the
controller
Appropriate
tightening torque:
0.25 N
•
m
Insert the controller
into the opening at
the front of the panel.
CAUTION
• Tighten the screws with appropriate tightening torque within 0.25 N•m.
Otherwise it may cause the case deformation or the bracket damage.
• Make sure that foreign materials do not enter the inside of the
instrument through the case’s slit holes.
■
External Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]
117 (4.61) min.
145 (5.71)
min.
+0.8
0
+0.8
0
92
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11
(0.43)
UT35A
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
Bracket
Bracket
94.6 (3.72)
91.6 (3.61)
105.2 (4.14)
Unit: mm (approx. inch)
96 (3.78)
96 (3.78)
• General mounting
• Side-by-side close mounting
Terminal cover
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8
0
92
+0.03
0
(3.62 )
(0.98)
+0.03
0
(3.62 )
+0.8
0
92
+0.03
0
(3.62 )
([(N-1)×3.78+3.62] )
+0.03
0
[(N-1)×48+45]
+0.6
0
65 (2.56)
48 (1.89)
11 (0.43)
UT32A
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
Bracket
Bracket Terminal cover
94.6 (3.72)
96 (3.78)
105.2 (4.14)
Unit: mm (approx. inch)
70 (2.76)
min.
(25)
145 (5.71)
min.
+0.6
0
45
(53) (2.09)
+0.8
0
92
• General mounting
• Side-by-side close mounting
20 (0.79)
91.6 (3.61)
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N
≥
5.
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.03
0
(3.62 )
+0.02
0
(1.77 ) (0.98)
+0.8
0
92
+0.03
0
(3.62 )
([(N-1)×1.89+1.77] )
+0.02
0
4. Hardware Specifications
WARNING
This instrument is for Measurement Category No.1.
Do not use it for measurements in locations falling under Measure-
ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance IV
Cable
III
T
O( I )
II
Category
IEC/EN/CSA
/
UL
61010-1
EN 61010-2-030
Remarks
No.1
Measurement
Category I
O (Other)
For measurements performed on circuits not direct
-
ly connected to MAINS.
No.2
Measurement
Category II
Measurement
Category II
For measurements performed on circuits directly
connected to the low-voltage installation.
No.3
Measurement
Category III
Measurement
Category III
For measurements performed in the building instal-
lation.
No.4
Measurement
Category IV
Measurement
Category IV
For measurements performed at the source of the
low-voltage installation.
■
Input Specifications
●Universal Input (Equipped as standard)
• Number of inputs: 1
• Input type, instrument range, and measurement accuracy: See the table below,
Input Type
Instrument Range
Accuracy
ºC
ºF
Thermo-
couple
K
-270.0 to 1370.0ºC -450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for
0°C or more
±0.2% of instrument range ±1 digit for
less than 0°C
±2% of instrument range ±1 digit for
less than -200.0°C of thermocouple K
±1% of instrument range ±1 digit for
less than -200.0°C of thermocouple T
-270.0 to 1000.0ºC -450.0 to 2300.0ºF
-200.0 to 500.0ºC
-200.0 to 1000.0ºF
J
-200.0 to 1200.0ºC -300.0 to 2300.0ºF
T
-270.0 to 400.0ºC
-450.0 to 750.0ºF
0.0 to 400.0ºC
-200.0 to 750.0ºF
B
0.0 to 1800.0ºC
32 to 3300ºF
±0.15% of instrument range ±1 digit
for 400°C or more
±5% of instrument range ±1 digit for
less than 400°C
S
0.0 to 1700.0ºC
32 to 3100ºF
±0.15% of instrument range ±1 digit
R
0.0 to 1700.0ºC
32 to 3100ºF
N
-200.0 to 1300.0ºC -300.0 to 2400.0ºF
±0.1% of instrument range ±1 digit
±0.25% of instrument range ±1 digit
for less than 0°C
E
-270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for
0°C or more
±0.2% of instrument range ±1 digit for
less than 0°C
±1.5% of instrument range ±1 digit for
less than -200.0°C of thermocouple E.
L
-200.0 to 900.0ºC
-300.0 to 1600.0ºF
U
-200.0 to 400.0ºC
-300.0 to 750.0ºF
0.0 to 400.0ºC
-200.0 to 1000.0ºF
W
0.0 to 2300.0ºC
32 to 4200ºF
±0.2% of instrument range ±1 digit
(Note 2)
Platinel 2
0.0 to 1390.0ºC
32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit
PR20-40
0.0 to 1900.0ºC
32 to 3400ºF
±0.5% of instrument range ±1 digit for
800°C or more
Accuracy is not guaranteed for less
than 800°C.
W97Re3-
W75Re25
0.0 to 2000.0ºC
32 to 3600ºF
±0.2% of instrument range ±1 digit
RTD
JPt100
-200.0 to 500.0ºC
-300.0 to 1000.0ºF ±0.1% of instrument range ±1 digit
(Note 1)
-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit
Pt100
-200.0 to 850.0ºC
-300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit
(Note 1)
-200.0 to 500.0ºC
-300.0 to 1000.0ºF
-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit
Standard signal
0.400 to 2.000 V
±0.1% of instrument range ±1 digit
1.000 to 5.000 V
DC voltage/current
0.000 to 2.000 V
0.00 to 10.00 V
-10.00 to 20.00 mV
0.0 to 100.0 mV
The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power
frequency at 50/60 Hz.
Note
1: ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range
between -100 and 200°C.
Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988
• Input sampling (control) period: 200 ms
• Burnout detection:
Functions at TC, RTD, and standard signal.
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4 mA or less.
• Input bias current: 0.05 µA (for TC or RTD)
• Measured current (RTD): About 0.16 mA
• Input resistance:
TC or mV input: 1 MΩ or more
V input: About 1 MΩ
• Allowable signal source resistance:
TC or mV input: 250 Ω or less
Effects of signal source resistance: 0.1 µV/Ω or less
DC voltage input: 2 kΩ or less
Effects of signal source resistance: About 0.01%/100 Ω
• Allowable wiring resistance:
RTD input: Max. 150 Ω/wire (The conductor resistance between the three wires
shall be equal.)
Wiring resistance effect: ±0.1ºC/10 Ω
• Allowable input voltage/current:
TC, mV and RTD input: ±10 V DC
V input: ±20 V DC
• Noise rejection ratio:
Normal mode: 40 dB or more (at 50/60 Hz)
Common mode: 120 dB or more (at 50/60 Hz)
For 100-240 V AC, the power frequency can be set manually. Automatic
detection is also available.
For 24 V AC/DC, the power frequency can be set manually.
• Reference junction compensation error:
±1.0ºC (15 to 35ºC), ±1.5ºC (-10 to 15ºC and 35 to 50ºC)
• Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD
●Remote Input with Direct Input
• Use: Remote setpoint setting, external compensating input, auxiliary input for com-
putation, etc.
• Number of inputs: See the table of Model and Suffix Codes.
• Input type, instrument range, and measurement accuracy: See the table below.
Input Type
Instrument Range
Accuracy
Standard signal
0.400 to 2.000 V
±0.2% of instrument range ±1 digit
1.000 to 5.000 V
±0.1% of instrument range ±1 digit
DC voltage
0.000 to 2.000 V
±0.2% of instrument range ±1 digit
0.00 to 10.00 V
±0.1% of instrument range ±1 digit
DC voltage
for high-input
impedance
0.000 to 1.250 V
±0.1% of instrument range ±1 digit
• Input sampling (control) period: Same as universal input
• Input resistance: About 1 MΩ
However, 10 MΩ or more for DC voltage for high-input impedance range
• Burnout detection: Functions at standard signal
Burnout is determined to have occurred if it is 0.1 V or less.
■
Contact Input Specifications
• Number of inputs: See the table of Model and Suffix Codes.
• Input type: No-voltage contact input or transistor contact input
• Input contact rating: 12 V DC, 10 mA or more
Use a contact with a minimum on-current of 1 mA or less.
• ON/OFF detection:
No-voltage contact input:
Contact resistance of 1 kΩ or less is determined as “ON” and contact
resistance of 50 kΩ or more as “OFF.”
Transistor contact input:
Input voltage of 2 V or less is determined as “ON” and leakage current must
not exceed 100 µA when “OFF.”
• Minimum status detection hold time: Control 50 ms
• Use: SP switch, operation mode switch, and event input
■
Analog Output Specifications
• Number of outputs:
Control output: 1
Cooling-side control output of Heating/cooling type (Retransmission output
terminal): 1
• Output type: Current output or voltage pulse output
• Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less
• Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)
The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH,
and power frequency at 50/60 Hz.
• Voltage pulse output:
Use: Time proportional output
On-voltage: 12 V or more/load resistance of 600 Ω or more
Off-voltage: 0.1 V DC or less
Time resolution: 10 ms or 0.1% of output, whichever is larger
■
Retransmission Output Specifications
• Number of outputs: Retransmission output; 1, shared with 15 V DC loop power
supply or Cooling-side control output.
• Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 Ω or less
• Current output accuracy (conversion accuracy from PV display on the set scale):
±0.1% of span (±5% of span for 1 mA or less)
The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH,
and power frequency at 50/60 Hz.
This is not conversion accuracy through input and output but the performance of
transmission output itself.
■
15 V DC Loop Power Supply Specifications
(Shared with retransmission output or Cooling-side control output.)
• Power supply: 14.5 to 18.0 V DC
• Maximum supply current: About 21 mA (with short-circuit current limiting circuit)
■
Step Response Time Specifications
Within 1 s (63% of analog output response time when a step change of 10 to 90% of
input span is applied)
■
Relay Contact Output Specifications
• Contact type and number of outputs:
Control output: contact point 1c; 1 point
Heating/cooling type: contact point 1a; 2 points for both heating and cooling sides
Alarm output: contact point 1a; 3 points (common is independent)
• Contact rating:
Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load)
Contact point 1a (control output): 240 V AC, 3A or 30 V DC, 3A (resistance load)
Contact point 1a (alarm output): 240 V AC, 1A or 30 V DC, 1 A (resistance load)
• Use: Time proportional output, alarm output, FAIL output, etc.
• Time resolution of control output: 10 ms or 0.1% of output, whichever is larger
Note: The control output should always be used with a load of 10 mA or more.
The alarm output should always be used with a load of 1 mA or more.
■
Transistor Contact Output Specifications
• Number of outputs: See the table of Model and Suffix Codes.
• Output type: Open collector (SINK current)
• Output contact rating: Max. 24 V DC, 50 mA
• Output time resolution: Min. 200 ms
• Use: Alarm output, FAIL output, etc.
■
Position Proportional Output Specifications
• Position signal input:
Slide resistance: 100 Ω to 2.5 kΩ of total resistance
100% side and slide line: with disconnection detection
0% side: without disconnection detection
Current input: 4 to 20 mA (with disconnection detection)
• Sampling period: 50 ms
• Measurement resolution: 0.1% of input span
• Position proportional relay output:
UT35A: contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)
UT32A: contact point 1a; 2 points, 240 V AC, 3 A or 30 V DC, 3 A (resistance load)
Note: This should always be used with a load of 10 mA or more.
■
Heater Break Alarm Specifications
• Number of inputs: 2
• Number of outputs: 2 (transistor contact output)
• Use: Measures the heater current using an external current transformer (CT) and
generates a heater break alarm when the measured value is less than the break
detection value.
• Current transformer input resistance: About 9.4 Ω
•
Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be applied.)
• Heater current setting range: OFF, 0.1 to 300.0 Arms
Heater current measured value display range: 0.0 to 360.0 Arms
Note: The CT ratio can be set. CT ratio setting range: 1 to 3300
• Recommended CT: CT from U.R.D., Ltd.
CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms
CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms
• Heater current measurement period: 200 ms
• Heater current measurement accuracy: ±5% of current transformer input range
span ± 1digit (CT error is not included.)
•
Heater current detection resolution: Within 1/250 of current transformer input range span
• Break detection On-time: Min. 0.2 second (for time proportional output)
■
24 V DC Loop Power Supply Specifications
• Use: Power is supplied to a 2-wire transmitter.
• Power supply: 21.6 to 28.0 V DC
• Rated current: 4 to 20 mA DC
• Maximum supply current: About 30 mA (with short-circuit current limiting circuit.)
■ Safety and EMC Standards
• Safety:
Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-2-201 (CE), IEC/EN 61010-
2-030 (CE), approved by CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL
61010-1.
Installation category: II
Pollution degree: 2
Measurement category: I (CAT I) (UL, CSA)
O (Other) (CE)
Rated measurement input voltage: Max. 10 V DC
Rated transient overvoltage: 1500 V (*)
* This is a reference safety standard value for measurement category I of CSA/UL 61010-
1, and for measurement category O of IEC/EN 61010-2-030. This value is not necessarily a
guarantee of instrument performance.
• EMC standards:
Compliant with CE marking
EN 61326-1 Class A, Table 2 (For use in industrial locations),
EN 61326-2-3
* The instrument continues to operate at a measurement accuracy of within ±20% of the
range during testing.
EN 55011 Class A, Group 1
EN 61000-3-2 Class A
EN 61000-3-3
EMC Regulatory Arrangement in Australia and New Zealand (for all model includ-
ing LL50A)
EN 55011 Class A, Group 1
• KC marking:
Electromagnetic wave interference prevention standard, electromagnetic wave
protection standard compliance.