background image

IM 05P01D31-81EN  page 5/12

Contents

1.   Names and Functions of Display Parts

2.   Setup  Procedure

3.   Quick Setting Function (Setting of Input and Output)

4.  

Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)

5.   Setting Alarm Type

6.   Setting Alarm Setpoint

1.  Names and Functions of Display Parts

(2) + (3) + (4) : Setpoint display

(1)

(2)

(9)

(10)

(11)

(4)

(8)

(10)

(9)

(3)
(5)
(6)

(7)

(8)

(2)

(3)

(4)
(5)
(6)

(11)

No. in figure

Name

Description

(1)

PV display 

 

(white or red)

Displays PV.

Displays an error code if an error occurs.

Displays the scrolling guide in the Menu Display and Parameter 

Setting Display when the guide display ON/OFF is set to ON.

(2)

Group display (green)

Displays a group number (1 to 4 or R) and terminal area (E1 to E4).

1 to 4 represent SP numbers in the Operation Display.

R and E1 to E4 are displayed in the Parameter Setting Display.

(3)

Symbol display (orange) Displays a parameter symbol.

(4)

Data display (orange) Displays a parameter setpoint and menu symbol.

(5)

Bar-graph display 

(orange)

Displays control output value (OUT) and measured input value (PV).

The data to be displayed can be set by the parameter.

Initial value: Deviation, Heating-side control output (in Heating/

cooling control)

(6)

Event indicator 

 

(orange)

Lit when the alarms 1 to 4 occur.

Event displays other than alarms can be set by the parameter.

(7)

Key navigation indica-

tor (green)

Lit or blinks when the Up/Down or Left/Right arrow key operation 

is possible.

(8)

Parameter display level 

indicator (green)

Displays the setting conditions of the parameter display level func-

tion.

Parameter display level

EASY

PRO

Easy setting mode

Lit

Unlit

Standard setting mode

Unlit

Unlit

Professional setting mode

Unlit

Lit

(9)

Status indicator 

(green and red)

Displays the operating conditions and control status.

Indicator

Description 

REM

Lit when in remote mode (REM).

STOP

Lit when in stop mode (STOP).

MAN

Lit when in manual mode (MAN). 

Blinks during auto-tuning.

(10)

Security indicator (red) Lit if a password is set. The setup parameter settings are locked.

(11)

Ladder operation 

indicator (green)

Lit while the ladder operation is executed.

(4)

(5)
(6)

(1)
(2)

(3)

(4)

(5)

(6)

(1)

(2)

No. in figure

Name

Description

(1)

UT35A: DISPLAY key

UT32A: DISP key

Used to switch the Operation Displays.

Press the key in the Operation Display to switch the provided 

Operation Displays.

Press the key in the Menu Display or Parameter Setting Display 

to return to the Operation Display.

(2)

UT35A: 

PARAMETER key

UT32A: PARA key

Hold down the key for 3 seconds to move to the Operation 

Parameter Setting Display.

Hold down the key and the Left arrow key simultaneously for 3 

seconds to move to the Setup Parameter Setting Display.

Press the key in the Parameter Setting Display to return to the 

Menu Display. Press the key once to cancel the parameter set-

ting (setpoint is blinking).

(3)

SET/ENTER key

Up/Down/Left/Right 

arrow keys

SET/ENTER key

  Press the key in the Menu Display to move to the Parameter 

  Setting Display of the Menu. Press the key in the Parameter 

  Setting Display to transfer to the parameter setting mode 

  (setpoint is blinking), and the parameter can be changed.

  Press the key during parameter setting mode to register the 

  setpoint.

Up/Down/Left/Right arrow keys

  Press the Left/Right arrow keys in the Menu Display to switch 

  the Displays.

  Press the Up/Down/Left/Right arrow keys in the Parameter 

  Setting Display to switch the Displays.

  Press the Up/Down arrow keys during parameter setting mode

  (setpoint is blinking) to change a setpoint.

  Press the Left/Right arrow keys during parameter setting mode

  

(setpoint is blinking) to move between digits according to the parameter.

(4)

Light-loader interface

It is the communication interface for the adapter cable used when 

setting and storing parameters from a PC. The LL50A Parameter 

Setting Software (sold separately) is required.

(5)

A/M key

Used to switch between AUTO and MAN modes.

The setting is switched between AUTO and MAN each time the 

key is pressed.

(6)

User function keys

The UT35A has F1, F2, and Fn keys.

The UT32A has only the Fn key. The user can assign a function 

to the key. The function is set by the parameter. 

Note:  The communication connector (maintenance port) for LL50A Parameter Setting Software is 

on the top of the unit. 

2.  Setup Procedure

The following flowchart shows the setup procedure for UT35A/UT32A. 

Install and wire a controller.

Monitoring and control of regular operations

Adjust PID using auto-tuning or manually for PID control.

 

Other setup

Operation

NO

NO

NO

YES

YES

YES

Set the other parameters as needed.

PID tuning

Input setup

Output setup

Installation

and wiring

Power ON

Control type setup

Control type setup

Input/output setup

Valve position

adjustment

Use

Quick setting

function?

Position

proportional

type?

Position

proportional

type?

For Position proportional type

3.  Quick Setting Function (Setting of Input and Output)

The Quick setting function is a function to easily set the basic function of the control-

ler.

Turn on the controller to start the Quick setting function.

This function allows you to easily set the control type, input, and output, and quickly 

start the control action.

The items (parameters) to be set by Quick setting function are as follows.

(1) Control type (PID control, Heating/cooling control, etc.)

(2) Input function (PV input type, range, scale (at voltage input), etc.)

(3) Output function (control output type and cycle time)

After turning on the controller, first decide whether or not to use the Quick setting func-

tion.

Operation in Initial Display

·  Press the SET/ENTER key while YES is displayed to start the Quick setting function.

·  If you change YES to NO and press the SET/ENTER key, Operation Display will 

appear without starting the Quick setting function.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

Operation

Guide

Initial Settings

UT35A/RSP, UT32A/RSP

Digital Indicating Controller 

(Non-isolated Remote Input Type)

Operation Guide

This operation guide describes basic settings and operations of the UT35A/UT32A.

For details of each function, see the electronic manual.

The scrolling guide is displayed on PV display in the Parameter Setting Display.

This guide can be turned on/off with the Fn key. 

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Standard Code Model»

 

(Panel Mounting Type)

·  To change and set the parameter setting, press the SET/ENTER key to start the 

setpoint blinking. The blinking state allows you to make changes (setting mode). 

Use the Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/EN-

TER key to register the setting.

  Making Settings Using Quick Setting Function

Example:  Setting to PID control, thermocouple type K (range of 0.0 to 

500.0

0

C), and current control output

For the detailed procedure and switching of displays, see "Flow of Quick Setting 

Function" below. For the parameters to set, see the next page. 

(1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.

(2) Set the control type parameter (CNT) to PID (PID control).

(3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0 

0

C). 

(4) Set the PV input unit parameter (UNIT) to C (Degree Celsius).

(5) Set the maximum value of PV input range parameter (RH) to 500.0.

(6) Set the minimum value of PV input range parameter (RL) to 0.0.

(7) Set the output type selection parameter (OT) to OUT terminals (current=00.02).

(8) Finally, EXIT is displayed. Change NO to YES and press the SET/ENTER key to 

complete the setup. Operation Display appears. 

Press the SET/ENTER key while YES 

is displayed to start the Quick setting.

[

NO

]

Select NO with the Down 

arrow key and press the 

SET/ENTER key.

Select NO to return to

 the Operation Display.

Power-on

First, the control type 

parameter (CNT) 

is displayed.

Initial value: PID (PID control)

 

Press the Down arrow key.

The PV input type 

parameter (IN) is 

displayed.

Initial value: OFF

Press the SET/ENTER key.

OFF blinks.

Blinking allows you to 

change the setting.

 

Press the Up arrow key.

K1 is displayed.

K1 has been registered.

Press the SET/ENTER key.

 

Press the Down arrow key.

[YES]

1.

2.

3.

4.

5.

6.

Quick setting starts

■  Flow of Quick Setting Function

In Quick setting mode, the parameter guide appears on PV display.

This guide can be turned on/off with the Fn key.

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) 

has been changed to 500.0.

The setpoint for the parameter RH has been registered.

Press the Down arrow key.

Operation Display

8.

9.

10.

11.

12.

The PV input unit parameter (UNIT) is displayed.

Initial value: C (Degree Celsius)

7.

Press the Down arrow key.

Follow the same procedure to set RL 

to 0.0 and OT to 00.02.

Set other parameters as needed.

Displays the measured 

input value (PV).

Displays the target 

setpoint (SP).

Finally, EXIT is displayed.

Press the SET/ENTER key to swtich to the setting mode.

Change NO to YES and press the SET/ENTER key 

to complete the setup of the basic function.

Operation Display appears.

The Quick setting function continues in the NO state. 

The upper limit value of the setting range is displayed 

for the parameter RH (maximum value of PV input range). 

Press the SET/ENTER key.

Press the SET/ENTER key.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and the Left/Right arrow 

keys to move between digits.

Содержание UT32A/RSP

Страница 1: ...rman French and Spanish are available for the guide display 2 The LP option can be specified in the combination of Type 2 code any of 0 or 1 and Type 3 code any of 0 or 1 3 The HA option can be specified only when the Type 1 code is 0 or 2 4 When the CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Products with CT option are not intended for EEA ...

Страница 2: ...input for com putation etc Number of inputs See the table of Model and Suffix Codes Input type instrument range and measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrumen...

Страница 3: ...ires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a life span resistance load of 100 000 times use the auxiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay f...

Страница 4: ... Relay contact output NC NO COM Contact rating 250 V AC 3 A 30 V DC 3 A resistance load 111 301 302 303 304 305 306 307 308 309 310 311 312 201 202 203 204 205 206 207 208 210 101 102 103 104 105 106 107 108 109 110 211 212 Current voltage pulse output 0 20 mA DC 4 20 mA DC Voltage pulse 12 V Heating cooling control output Suffix code Type 1 2 Cooling side control output Heating cooling relay cont...

Страница 5: ...ntrol type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the controller to start the Quick setting function This function allows ...

Страница 6: ...RM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY key or DISP key once to return to the Operation Display Symbol To change the alarm type change the last 2 digits of th...

Страница 7: ... User s Manual IM 05P01D31 01EN The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp blinks The OUT symbol appears The output values at 100 0 and 0 appear altern...

Страница 8: ...ystem data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repa...

Страница 9: ...Without Stand by action 0 PV low limit 02 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high limit 12 Target SP deviation low limit 13 Target ...

Страница 10: ...re not described in this manual See User s Manual IM 05P01D31 01EN Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting Range Initial value User setting Display level CNT Control type PID PID control ONOF ON OFF control 1 point of hysteresis ONOF2 ON OFF control 2 points of hysteresis 2P2L Two position two level control H C Heating cooling control PID or H ...

Страница 11: ...cation with checksum LADR Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loop 2 mode P P Peer to peer communication MBRTU EASY BPS Baud rate 600 600 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI ...

Страница 12: ...error status LA ER Ladder error status MCU MCU version DCU DCU version ECU1 ECU 1 version E1 terminal area ECU3 ECU 3 version E3 terminal area ECU4 ECU 4 version E4 terminal area PARA Parameter version H VER Product version SER1 Serial number 1 SER2 Serial number 2 MAC1 MAC address 1 E3 terminal area MAC2 MAC address 2 E3 terminal area MAC3 MAC address 3 E3 terminal area Parameter Display Level Pa...

Отзывы: