background image

IM 05C01E12-41E

15

 Parameter Lists

(SP value display)

Target 
setpoint

Minimum value (SPL) to maximum value (SPH) of target setpoint range
Unit: 

°

C/

°

F

SPL

CTL

Control mode

ONF(0): On/off control
PID(1): PID control
SLF(2): Dynamic auto tune control (cannot be set for heating/cooling control)

SLF(2) :for standard type;
PID(1) : for 

heating/cooling type

AT

Auto-tuning

OFF(0): Stop auto-tuning
ON(1): Start auto-tuning

OFF(0)

P

Proportional 
band

1

°

C/

°

F to the temperature that corresponds to 100% of the 

measured input range (scale) span

5% of measured 
input range (scale) 
span

I

Integral time

1 to 3600 seconds; 
OFF(0): no integral action

240 seconds

D

Derivative 
time

1 to 3600 seconds; 
OFF(0): no derivative action

60 seconds

MR

Manual reset

–100 to 100%

50.0% for standard type; 
0.0% for 
heating/cooling type

COL

Cooling-side 
gain

0.01 to 9.99 times

1.00 times

DB

Deadband

0% of measured 
input range (scale) 
span

HYS

Hysteresis for 
on/off control

0

°

C/

°

F to the temperature that corresponds to 100% of the 

measured input range (scale) span 

0.5% of measured 
input range (scale) 
span

CT

Control output
 cycle time

1 to 240 seconds

30 seconds

CTC

Cooling-side 
control output 
cycle time

1 to 240 seconds

30 seconds

SP1

Target 
setpoint 1

Minimum value (SPL) to maximum value (SPH) of target 
setpoint range
Unit: 

°

C/

°

F

There are also optional engineering units for voltage input.

SPL

SP2

Target 
setpoint 2

SPL

FL

PV input filter

OFF(0), 1 to 120 seconds

OFF(0)

BS

PV input bias

–100 to 100% of measured input range (scale) span

0% of measured 
input range (scale) 
span

LOC

Key lock

T1

Timer
setting 1

0.0 to 99.59
Unit: minutes and seconds or hours and minutes
Set the timer time unit using parameter TTU.

For example, 15.25 sets 15 minutes and 25 seconds.
(T1 is for AL1, and T2 is for AL2)

0.00

T2

Timer 
setting 2

0.00

(2) Operating Parameters : Parameters changed rather frequently during operation.

HC

Heater disconnection 
current measured 
value

“HC” is not a parameter to be set. The current value (0 to 80) of heater disconnection 
detector is displayed.    Unit: A (ampere)
Settings: When the display value is – – – –, the heater current is not being measured.

A1

Alarm 1
setpoint

Max. value of 
measured input range 
(scale) (PV alarm)

A2

Alarm 2
setpoint

Min. value of 
measured input range 
(scale) (PV alarm)

0: No key lock
1: Prevents operations from being changed except for the 

changing of SP in the operating display

2: Prevents all parameter changing operations
–1: Set 

-1

 to enter the setup parameter setting display.

      But if  

LOC=1 or 2

 is already set, the parameter value can 

not be changed by setting 

LOC=-1

 only. To change the 

parameter value, set 

LOC=0

 at first (for disabling keylock), 

then set 

LOC=-1

 once again.

0

(1) Target Setpoint (SP) and Timer Setting 1 and 2

Code

Name

Setting range and unit

Default

User setting

Code

Setting range and unit

Default

User setting

 PV alarm    Unit: 

°

C/

°

F

Setting range: minimum value to maximum value of 
measured input range (scale)

 Deviation alarm    Unit: 

°

C/

°

F

Setting range: –100 to 100% of the measured input range (scale) span

 Heater disconnection alarm    Unit: A (ampere) 

Setting range: OFF(0), 1 to 80 
(can be set for the alarm 1 setpoint only)

 PID control    Unit: 

°

C/

°

F

Setting range: –(proportional band setting) to +(proportional band setting)

 On/off control    Unit: 

°

C/

°

F

Setting range: –50 to +50% of measured input range (scale)span

Name

Numbers in ( ) are the parmeter setpoints that apply when the 
communication function is used. Ex. OFF(0), ON(1)

Содержание UT150

Страница 1: ...User s Manual Models UT150 UT152 UT155 Temperature Controllers IM 05C01E12 41E IM 05C01E12 41E 2004 6 4th Edition...

Страница 2: ...e both manuals have the same contents except for some minor differences in the cross referenced page numbers Revision Record Manual No IM 05C01E12 41E 4th Edition Title Models UT150 UT152 UT155 Temper...

Страница 3: ...20mA output continuous PID Option AL HBA EX RET RS V24 Alarm outputs 2 points Heater disconnection alarm includes optional AL function SP1 SP2 switching starting of timer and RUN STOP switching by ex...

Страница 4: ...fe The following symbols are used in this manual only NOTE Indicates that operating the hardware or software in a particular manner may lead to damage or result in system failure IMPORTANT Draws atten...

Страница 5: ...ol the left upper lamp lights up in orange when the heating side output is active while the right lower lamp lights up in green when the cooling side output is active g Data change keys Indicated as s...

Страница 6: ...close the controller in shielding panels positioned at least 150mm away from each side These panels should be made of either 1 43mm thick metal plated steel plates or 1 6mm thick uncoated steel plates...

Страница 7: ...T155 N is the number of controllers If N 5 then measure the actual length N 1 96 92 0 8 0 1 1021 301 20 min 70 48 min 145 92 0 8 0 45 0 6 0 max 44 6 max 91 8 max 112 100 96 Panel thickness 1 to 10 11...

Страница 8: ...n the 3 wires See the table given later for the specifications of the cables and terminals and the recommended products 3 The control output relay cannot be replaced even though it has a limited servi...

Страница 9: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TC Input DC mV or V Input RTD Input 7 8 7 8 6 7 8 B b A NO COM ALM2 ALM1 COM Relay Contact Output 4 to 20 mA DC Output Voltage Pulse Output Heating side Control Out...

Страница 10: ...stand for the polarity for DC 24V power supply UT152 UT155 Terminal Arrangement Heating cooling type 11 21 22 23 24 25 26 27 28 29 30 12 13 14 15 16 17 18 19 20 TC Input DC mV or V Input RTD Input 12...

Страница 11: ...tandards The communication function is provided only when the RS option is specified For details read the user s manual of the communications function IM 05C01E12 10E Communication Protocol Personal c...

Страница 12: ...155 For side by side close installation the controller loses its dust proof and drip proof protection Casing ABS resin and polycarbonate Case color Black Mounting Flush panel mounting Power Supply and...

Страница 13: ...2 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 Thermocouple RTD DC voltage K J T E R S B N L U Platinel 2 Pt100 JPt100 0 to 100mV 0 to 5V 1 to 5V 0 to 10V Unspecified 270 to 1370 C 0 0 to 600 0 C 0...

Страница 14: ...n explains how to set and register parameter values The procedure for changing SP target setpoint and A1 alarm 1 setpoint can be found on Changing Target Setpoint SP and Changing Alarm 1 Setpoint A1 r...

Страница 15: ...y for at least 3 seconds If your controller has the AL or HBA option the display for the Alarm 1 setpoint A1 appears If not control mode CTL appears Press for at least 3 seconds Step 3 Press the key o...

Страница 16: ...ONF on off control CTL PID Displayed when I OFF Displayed for heating cooling type Displayed for heating cooling type Displayed for time proportional PID control Displayed for time proportional PID c...

Страница 17: ...ds or hours and minutes Set the timer time unit using parameter TTU For example 15 25 sets 15 minutes and 25 seconds T1 is for AL1 and T2 is for AL2 0 00 T2 Timer setting 2 0 00 2 Operating Parameters...

Страница 18: ...UPER function Note Not displayed when on off control OFF 0 DR Direct reverse action 0 Reverse action 1 Direct action Note Not displayed for heating cooling type 0 ADR Controller address 1 to 99 Howeve...

Страница 19: ...n on Alarm setting Measured value Measured value Temperature setpoint Hysteresis Deviation setting Opn on Cls off The output contact is opened in the following events Program error ROM error RAM error...

Страница 20: ...is function operates at the following events a SP change b SP1 SP2 switching c Power on At power on SP starts from the current PV value Set the ramp rate time unit using parameter TMU The cycle time i...

Страница 21: ...P and then turn the controller off once and then back on again Do not use dynamic auto tune control for a system where there is interference or continual disturbances IMPORTANT To use dynamic auto tun...

Страница 22: ...proper values B o Input burnout Check the sensor wiring and correct it OOO PV over scale PV exceeds its effective range Check the input type and range settings and correct them Press any key to stop...

Страница 23: ......

Страница 24: ...SUL S A Headquarters Plant Praca Acapulco 31 Santo Amaro Sao Paulo SP BRAZIL CEP 04675 190 Phone 55 11 5681 2400 Facsimile 55 11 5681 4434 YOKOGAWA ENGINEERING ASIA PTE LTD Head office 5 Bedok South...

Отзывы: