background image

IM 05C01E12-41E

11

7.

KEY OPERATIONS

NOTE

At power-on, the temperature controller displays the operation display 

, but if the input range setting

remains OFF, then “IN” appears. In this case, press the 

 key to display the input range code you want to

use, then press the 

 key to register it. (Refer to the flowchart on page 13.)

(1) You can move between parameter setting displays using the 

 key.

(2) To change the set value,

(i) Change the display value with the 

 or 

 key

(the period flashes).

(ii) Press the 

 key to register the setting.

(3) At the operation display 

 or 

 , pressing the 

 key for at least 3

seconds retrieves the operation parameter setting display.

(4) At the operation parameter setting display, pressing the 

 key for at

least 3 seconds transfers back to the operation display 

. Registering the

key-lock parameter LOC to “–1” retrieves the setup parameter setting
display.

(5) At the setup parameter setting display, pressing the 

 key for at least 3

seconds transfers back to the operation display 

.

OFF









10 
11 
12 
13 
14 
15 
16 
17 
18 
19 
20 
21 
22 
23

31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48

Thermocouple

RTD

DC voltage

J

T



Platinel 2 

Pt100 

JPt100 

0 to 100mV 

0 to 5V 
1 to 5V 

0 to 10V

U n s p e c i f i e d

– 270 to 1370

°

C

0.0 to 600.0

°

0.0 to 400.0

°

– 199.9 to 200.0

°

– 199.9 to 999.9

°

– 199.9 to 400.0

°

– 199.9 to 999.9

°

0 to 1700

°

0 to 1700

°

0 to 1800

°

– 200 to 1300

°

– 199.9 to 900.0

°

– 199.9 to 400.0

°

0 to 1390

°

– 199.9 to 850.0

°

0.0 to 400.0

°

– 199.9 to 200.0

°

– 19.9 to 99.9

°

– 199.9 to 500.0

°

– 300 to 2500

°

F

32.0 to 999.9

°

32.0 to 750.0

°

– 300 to 400

°

– 300 to 2100

°

– 300 to 750

°

– 300 to 1800

°

32 to 3100

°

32 to 3100

°

32 to 3200

°

– 300 to 2400

°

– 300 to 1600

°

– 300 to 750

°

32 to 2500

°

– 199.9 to 999.9

°

32.0 to 750.0

°

– 300 to 400

°

– 199.9 to 999.9

°

For example, to select 
thermocouple type E (

°

F), 

set the range code to 37.

0.0 to 100.0 

0.000 to 5.000 
1.000 to 5.000 

0.00 to 10.00

User-scalable

 UT150/UT152/UT155 Measured Input Ranges

Input type

Range 

(

°

C

)

Range 

(

°

F

)

Range code 

(

°

C

)

Range code 

(

°

F

)

When “In” appears, press the         
key to display the measured input 
range code you want to use, then 
press the           key to register it. 
After this operating, the controller 
shows the operating display 

.

NOTE

Note:

If you cannot change

the parameter setting
value, check the key-lock
parameter (LOC) setting.

Содержание UT150

Страница 1: ...User s Manual Models UT150 UT152 UT155 Temperature Controllers IM 05C01E12 41E IM 05C01E12 41E 2004 6 4th Edition...

Страница 2: ...e both manuals have the same contents except for some minor differences in the cross referenced page numbers Revision Record Manual No IM 05C01E12 41E 4th Edition Title Models UT150 UT152 UT155 Temper...

Страница 3: ...20mA output continuous PID Option AL HBA EX RET RS V24 Alarm outputs 2 points Heater disconnection alarm includes optional AL function SP1 SP2 switching starting of timer and RUN STOP switching by ex...

Страница 4: ...fe The following symbols are used in this manual only NOTE Indicates that operating the hardware or software in a particular manner may lead to damage or result in system failure IMPORTANT Draws atten...

Страница 5: ...ol the left upper lamp lights up in orange when the heating side output is active while the right lower lamp lights up in green when the cooling side output is active g Data change keys Indicated as s...

Страница 6: ...close the controller in shielding panels positioned at least 150mm away from each side These panels should be made of either 1 43mm thick metal plated steel plates or 1 6mm thick uncoated steel plates...

Страница 7: ...T155 N is the number of controllers If N 5 then measure the actual length N 1 96 92 0 8 0 1 1021 301 20 min 70 48 min 145 92 0 8 0 45 0 6 0 max 44 6 max 91 8 max 112 100 96 Panel thickness 1 to 10 11...

Страница 8: ...n the 3 wires See the table given later for the specifications of the cables and terminals and the recommended products 3 The control output relay cannot be replaced even though it has a limited servi...

Страница 9: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TC Input DC mV or V Input RTD Input 7 8 7 8 6 7 8 B b A NO COM ALM2 ALM1 COM Relay Contact Output 4 to 20 mA DC Output Voltage Pulse Output Heating side Control Out...

Страница 10: ...stand for the polarity for DC 24V power supply UT152 UT155 Terminal Arrangement Heating cooling type 11 21 22 23 24 25 26 27 28 29 30 12 13 14 15 16 17 18 19 20 TC Input DC mV or V Input RTD Input 12...

Страница 11: ...tandards The communication function is provided only when the RS option is specified For details read the user s manual of the communications function IM 05C01E12 10E Communication Protocol Personal c...

Страница 12: ...155 For side by side close installation the controller loses its dust proof and drip proof protection Casing ABS resin and polycarbonate Case color Black Mounting Flush panel mounting Power Supply and...

Страница 13: ...2 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 Thermocouple RTD DC voltage K J T E R S B N L U Platinel 2 Pt100 JPt100 0 to 100mV 0 to 5V 1 to 5V 0 to 10V Unspecified 270 to 1370 C 0 0 to 600 0 C 0...

Страница 14: ...n explains how to set and register parameter values The procedure for changing SP target setpoint and A1 alarm 1 setpoint can be found on Changing Target Setpoint SP and Changing Alarm 1 Setpoint A1 r...

Страница 15: ...y for at least 3 seconds If your controller has the AL or HBA option the display for the Alarm 1 setpoint A1 appears If not control mode CTL appears Press for at least 3 seconds Step 3 Press the key o...

Страница 16: ...ONF on off control CTL PID Displayed when I OFF Displayed for heating cooling type Displayed for heating cooling type Displayed for time proportional PID control Displayed for time proportional PID c...

Страница 17: ...ds or hours and minutes Set the timer time unit using parameter TTU For example 15 25 sets 15 minutes and 25 seconds T1 is for AL1 and T2 is for AL2 0 00 T2 Timer setting 2 0 00 2 Operating Parameters...

Страница 18: ...UPER function Note Not displayed when on off control OFF 0 DR Direct reverse action 0 Reverse action 1 Direct action Note Not displayed for heating cooling type 0 ADR Controller address 1 to 99 Howeve...

Страница 19: ...n on Alarm setting Measured value Measured value Temperature setpoint Hysteresis Deviation setting Opn on Cls off The output contact is opened in the following events Program error ROM error RAM error...

Страница 20: ...is function operates at the following events a SP change b SP1 SP2 switching c Power on At power on SP starts from the current PV value Set the ramp rate time unit using parameter TMU The cycle time i...

Страница 21: ...P and then turn the controller off once and then back on again Do not use dynamic auto tune control for a system where there is interference or continual disturbances IMPORTANT To use dynamic auto tun...

Страница 22: ...proper values B o Input burnout Check the sensor wiring and correct it OOO PV over scale PV exceeds its effective range Check the input type and range settings and correct them Press any key to stop...