background image

IM 05C01E12-41E

18

 Description of Parameters

This section describes the parameter functions specific to the UT150/UT152/UT155 temperature controllers.
(The functions described in other sections of this manual and the general functions are not discussed.)

Parameter

Function

Parameter

Function

Control mode

CTL

Select one from the following:
a. Dynamic auto tune control (SLF) 

(See note)

b. PID control (PID)
c. On/off control (ONF)
Note: Dynamic auto tune control is not available 

for heating/cooling control.

Read the section below this table to find out more 
about dynamic auto tune control.

PV input bias

BS

This function adds a bias value to the measured input value, 
and the result is used for display and control computation.

This function is useful for carrying out fine adjustment when 
the PV value is within the required accuracy but it differs 
from the value obtained by other equipment.

Manual reset

MR

You can set this parameter only for control 
without an integral action (when registered as 
CTL=PID and I=OFF). The controller outputs the 
manual reset (MR) value when PV=SP. For 
example, if you set MR=50%, the controller 
outputs (OUT) 50% when PV=SP.

Cooling-side
gain 

COL

Maximum/minimum 
value of measured 
input scale

RH, 
RL

For heating/cooling control, you can set the ratio 
between the cooling-side output and heating-side 
output.
For example, if you set COL=2.0 and the heating-
side output is 10% at a certain deviation (SP-PV), 
then the cooling-side output will be 20% when the 
cooling-side also reaches that deviation.

Deadband

DB

You can only set a deadband for heating/cooling 
control. In a positive deadband, there are neither 
heating-side nor cooling-side outputs. In a 
negative deadband, there are both heating-side and 
cooling-side outputs, which overlap each other.

Maximum/minimum 
value of  
target setpoint range  

SPH, 
SPL

Using the SPH and SPL parameters, you can limit 
the setting range of the target setpoint (SP) within 
the measured input range(scale).

This function prevents SP from being mistakenly 
set at too large or too small a value (beyond the 
setting range). 

Hysteresis for 
on/off control 

HYS

For on/off control (CTL=ONF), you can set a 
hysteresis around the on/off point (SP) to prevent 
chattering.

Setpoint ramp
up/ramp-down 
rate

UPR, 
DNR

To prevent a sudden change in SP, or to change SP at a 
constant rate, ramp-up and ramp-down rates can be set 
separately. This function operates at the following events.
a. SP change
b. SP1/SP2 switching
c. Power-on
At power-on, SP starts from
the current PV value.

Set the ramp-rate time unit using parameter TMU.

The cycle time is the period of on/off repetitions 
of a relay or voltage pulse output in time 
proportional PID control. The ratio of the ON time 
to the cycle time is proportional to the control 
output value.

Hysteresis for 
alarm 1 and 2 

HY1,  
HY2

The alarms are output as relay outputs. Since a 
relay has a limited life, excessive on/off actions 
will shorten the life of the alarm. To prevent this, 
you can set a hysteresis to prevent excessive 
on/off actions for both alarm 1 and alarm 2.

PV input filter

FL

This function should be used when the PV display value 
may fluctuate greatly, for example, when the measured 
input signal contains noise. The filter is of the first-
order lag type, and FL sets the time constant. If a larger 
time constant is set, the filter can remove more noise.

SUPER  
function   
selection  

SC

The SUPER function is effective in the following cases:
a. An overshoot must be suppressed.
b. The rise-up time needs to be shortened.
c. The load often varies.
d. SP is changed frequently.
Note 1: The SUPER function will not work when 

on/off control is selected, or I or D 
constants is set at OFF in PID control.

Note 2: For some types of systems, the SUPER 

function may not be so useful.  If this is 
the case, turn off the function.

Decimal point 
of measurement
input

DP

For DC voltage input, the input signal can be scaled for the 
particular engineering unit. For example, if you set the input 
type (IN) at range code 22, the initial range is 0.0 to 100.0.
a. Using DP, set the decimal point position fit for the 

engineering unit you want to use. (In the example below, 
the 2 digits to the right of the decimal point)

b. Next, register the scale values of the measured input scale using 

RH and RL. (In the example below, RH=10.00 and RL=0.00)

Initial scale

100.0 (5V)

0.0 (1V)

10.00 (RH)

0.00 (RL)

Measured input scale 

(after being scaled)

Register the decimal point position using DP.

On/off point (SP)

Hysteresis

ON

OFF

Cycle time

t ON

t OFF

Input

HYS

HYS

ON

OFF

ON

OFF

Deadband

DB (+)

Deadband

DB (+)

0

SP

PV

100%

100

0

SP

100

PV

100%

Cooling 

side

Heating 

side

100%

         

0%

1. When the deadband of a heating/

cooling type is positive
(Proportional band [P] control)

2. When both the heating and cooling 

sides are under on-off control

PV value inside the controller

measured input value

PV bias

+

=

Ramp-rate
for n

°

C/min. 

or n

°

C/h.

Control output 
/ cooling-side 
control output
cycle time

CT 
CTC

2-seconds filter

10-seconds filter

Содержание UT150

Страница 1: ...User s Manual Models UT150 UT152 UT155 Temperature Controllers IM 05C01E12 41E IM 05C01E12 41E 2004 6 4th Edition...

Страница 2: ...e both manuals have the same contents except for some minor differences in the cross referenced page numbers Revision Record Manual No IM 05C01E12 41E 4th Edition Title Models UT150 UT152 UT155 Temper...

Страница 3: ...20mA output continuous PID Option AL HBA EX RET RS V24 Alarm outputs 2 points Heater disconnection alarm includes optional AL function SP1 SP2 switching starting of timer and RUN STOP switching by ex...

Страница 4: ...fe The following symbols are used in this manual only NOTE Indicates that operating the hardware or software in a particular manner may lead to damage or result in system failure IMPORTANT Draws atten...

Страница 5: ...ol the left upper lamp lights up in orange when the heating side output is active while the right lower lamp lights up in green when the cooling side output is active g Data change keys Indicated as s...

Страница 6: ...close the controller in shielding panels positioned at least 150mm away from each side These panels should be made of either 1 43mm thick metal plated steel plates or 1 6mm thick uncoated steel plates...

Страница 7: ...T155 N is the number of controllers If N 5 then measure the actual length N 1 96 92 0 8 0 1 1021 301 20 min 70 48 min 145 92 0 8 0 45 0 6 0 max 44 6 max 91 8 max 112 100 96 Panel thickness 1 to 10 11...

Страница 8: ...n the 3 wires See the table given later for the specifications of the cables and terminals and the recommended products 3 The control output relay cannot be replaced even though it has a limited servi...

Страница 9: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TC Input DC mV or V Input RTD Input 7 8 7 8 6 7 8 B b A NO COM ALM2 ALM1 COM Relay Contact Output 4 to 20 mA DC Output Voltage Pulse Output Heating side Control Out...

Страница 10: ...stand for the polarity for DC 24V power supply UT152 UT155 Terminal Arrangement Heating cooling type 11 21 22 23 24 25 26 27 28 29 30 12 13 14 15 16 17 18 19 20 TC Input DC mV or V Input RTD Input 12...

Страница 11: ...tandards The communication function is provided only when the RS option is specified For details read the user s manual of the communications function IM 05C01E12 10E Communication Protocol Personal c...

Страница 12: ...155 For side by side close installation the controller loses its dust proof and drip proof protection Casing ABS resin and polycarbonate Case color Black Mounting Flush panel mounting Power Supply and...

Страница 13: ...2 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 Thermocouple RTD DC voltage K J T E R S B N L U Platinel 2 Pt100 JPt100 0 to 100mV 0 to 5V 1 to 5V 0 to 10V Unspecified 270 to 1370 C 0 0 to 600 0 C 0...

Страница 14: ...n explains how to set and register parameter values The procedure for changing SP target setpoint and A1 alarm 1 setpoint can be found on Changing Target Setpoint SP and Changing Alarm 1 Setpoint A1 r...

Страница 15: ...y for at least 3 seconds If your controller has the AL or HBA option the display for the Alarm 1 setpoint A1 appears If not control mode CTL appears Press for at least 3 seconds Step 3 Press the key o...

Страница 16: ...ONF on off control CTL PID Displayed when I OFF Displayed for heating cooling type Displayed for heating cooling type Displayed for time proportional PID control Displayed for time proportional PID c...

Страница 17: ...ds or hours and minutes Set the timer time unit using parameter TTU For example 15 25 sets 15 minutes and 25 seconds T1 is for AL1 and T2 is for AL2 0 00 T2 Timer setting 2 0 00 2 Operating Parameters...

Страница 18: ...UPER function Note Not displayed when on off control OFF 0 DR Direct reverse action 0 Reverse action 1 Direct action Note Not displayed for heating cooling type 0 ADR Controller address 1 to 99 Howeve...

Страница 19: ...n on Alarm setting Measured value Measured value Temperature setpoint Hysteresis Deviation setting Opn on Cls off The output contact is opened in the following events Program error ROM error RAM error...

Страница 20: ...is function operates at the following events a SP change b SP1 SP2 switching c Power on At power on SP starts from the current PV value Set the ramp rate time unit using parameter TMU The cycle time i...

Страница 21: ...P and then turn the controller off once and then back on again Do not use dynamic auto tune control for a system where there is interference or continual disturbances IMPORTANT To use dynamic auto tun...

Страница 22: ...proper values B o Input burnout Check the sensor wiring and correct it OOO PV over scale PV exceeds its effective range Check the input type and range settings and correct them Press any key to stop...

Страница 23: ......

Страница 24: ...SUL S A Headquarters Plant Praca Acapulco 31 Santo Amaro Sao Paulo SP BRAZIL CEP 04675 190 Phone 55 11 5681 2400 Facsimile 55 11 5681 4434 YOKOGAWA ENGINEERING ASIA PTE LTD Head office 5 Bedok South...

Отзывы: