IM 05C01E12-41E
16
IN
Measured
input type
1 to 23, 31 to 48 (See input range code list.)
OFF(0): No input
(If no input type is specified at the time of ordering, you must set the input type.)
OFF(0), or the input
range code specified
with order
DP
Decimal point
position of
measured input
0: No decimal place (nnnn)
1: One decimal place (nnn.n)
2: Two decimal places (nn.nn)
3: Three decimal places (n.nnn)
1
RH
Maximum value
of measured
input scale
(RL + 1) to 9999
100.0
RL
Minimum value
of measured
input scale
–1999 to (RH –1)
0.0
SPH
Maximum value
of target setpoint
range
(SPL+1
°
C) to the maximum value of the measured input range
(scale) ; Unit:
°
C/
°
F
Maximum value of
measured input
range (scale)
SPL
Minimum value
of target setpoint
range
Minimum value of measured input range (scale) to (SPH –1
°
C)
Unit:
°
C/
°
F
Minimum value of
measured input
range (scale)
UPR
Setpoint ramp-
up-rate
OFF(0)
or a value from the minimum to the maximum value of the
measured input range (scale)
Unit:
°
C/min or
°
C/hour,
°
F/min or
°
F/hour
Set the ramp-rate time unit using parameter TMU.
OFF(0)
DNR
Setpoint ramp-
down-rate
OFF(0)
AL1
Alarm 1 type
OFF(0) or a value from 1 to 22 (see the table of alarm function
list), and either
23 or 24 (if the timer function [/EX option] is included), and
25 (if the heater disconnection function [/HBA option] is included)
1
(PV high limit alarm)
AL2
Alarm 2 type
OFF(0) or a value from 1 to 22 (see the table of alarm function
list), and either
23 or 24 (if the timer function [/EX option]) is included)
2
(PV low limit alarm)
HY1
Alarm 1
hysteresis
0 to 100% of measured input range (scale) span
Unit:
°
C/
°
F
0.5% of measured
input range (scale)
span
HY2
Alarm 2
hysteresis
SC
SUPER
function
ON(1): Uses the SUPER function
OFF(0): Does not use SUPER function
Note: Not displayed when on/off control
OFF(0)
DR
Direct/reverse
action
0: Reverse action
1: Direct action
Note: Not displayed for heating/cooling type
0
ADR
Controller
address
1 to 99
However, the number of controllers that can be connected per
host device is 31 at the maximum.
1
BPS
Baud rate
2.4(0): 2400 bps
4.8(1): 4800 bps
9.6(2): 9600 bps
9.6(2)
PRI
Parity
NON(0): Disabled
EVN(1); Even parity
ODD(2): Odd parity
EVN(1)
STP
Stop bit
1 or 2 bits
1 bit
DLN
Data length
7 or 8 bits
• 8 bits when ladder, MODBUS (RTU)
• 7 bits when MODBUS (ASCII)
8 bits
PSL
Protocol
selection
0: PC-link communication
1: PC-link communication with sum check
2: Ladder communication
3: MODBUS in ASCII mode
4: MODBUS in RTU mode
0
(3) Setup Parameters : Parameters rarely changed in normal use after once having been set.
TMU
Setpoint ramp-
rate time unit
0 :
°
C or
°
F / hour
1 :
°
C or
°
F / min
1
DIS
EOT
TTU
RTH
RTL
External Contact Inputs
21
22
23
SP2
STOP
TMR
STOP
COM
TMR
STOP
SP2
STOP
Parameter DIS
0
1
2
SP1/SP2
switching
SP2
when DI=ON
Timer starts
when DI=ON
Timer stops
when DI=OFF
Timer starts
when DI=ON
Timer stops
when DI=OFF
RUN/STOP
switching
STOP
when DI=ON
SP1/SP2
switching
SP2
when DI=ON
RUN/STOP
switching
STOP
when DI=ON
3
4
5
UT150 UT152
UT155
DI-function
selection
Output in STOP
mode
Timer time unit
Maximum value
of retransmission
output
Minimum value
of retransmission
output
In STOP mode by contact input, fixed control output can be
generated.
0 : 0%, 1 : 100%
0 : hour.minute
1 : minute.second
(Displayed at voltage input)
(Displayed at voltage input)
(Displayed at voltage input)
Temperature input : Within measured input range
Voltage input : RTL+1digit to max. value of measured input
(scale)(RH)
Min. value of measured input (scale)(RL) to RTH-1digit
However, RTL<RTH
Maximum value of
measured input range
(scale)
Minimum value of
measured input range
(scale)
0
0
1
Code
Name
Setting range and unit
Default
User setting