background image

IM 05C01E12-41E

9

6.

HARDWARE SPECIFICATIONS

 

Input: 1 point

 

Input type: Universal; can be selected by software 

 

Input accuracy (at 23 

±

2

°

C ambient temperature)

 Thermocouple: 

±

2

°

C

±

1digit

However,

• 

±

4

°

C for thermocouple input –200 to –100

°

C

• 

±

3

°

C for thermocouple input –100 to 0

°

C

• 

±

5

°

C for type R and S (

±

9

°

C for 0 to 500

°

C)

• 

±

9

°

C for type B (accuracy is not guaranteed for 0 to 400

°

C)

 RTD: 

±

1

°

C

±

1digit

  •

 Voltage (mV, V): 

±

0.3%

±

1digit

 

Sampling period for measured value input: 500ms

 

Burn-out detection: Functions for thermocouple or RTD input (burn-out upscale 

only; cannot be switched off)

 

Input resistance: 1M

 or greater for thermocouple or DC mV input.  Approx. 1M

 for DC V input  

 

Maximum allowable signal source resistance : 

                             250

 for thermocouple or DC mV input

                             2k

 for DC V input

 

Maximum allowable wiring resistance for RTD input: 10

/wire (The resistance values of 

three wires must be the same.)

 

Allowable input voltage: 

±

10V DC for thermocouple or DC mV input

 

±

20V DC for DC V input

 

Noise rejection ratio: Normal mode noise: Min. 40dB

  (50/60Hz) 

Common mode noise: Min. 120dB

(Min. 90dB for DC V input)

 

Error of reference junction compensation: 

±

1.5

°

C (at 15-35

°

C)

 

±

2.0

°

C (at 0-50

°

C)

The reference junction compensation cannot be switched off.

 

Applicable standards: Thermocouple and resistance temperature detector JIS/IEC/DIN (ITS90)

 

Output: 1 point (for standard type) or  2 points (for heating/cooling type)

 

Output type: Choose one from (1) to (3) below:

(1) Relay contact output
Contact capacity: 3A at 240V AC or 3A at 30V DC (with resistance load)
Note: The control output relay cannot be replaced by users.
(2) Voltage pulse output
On voltage: 12-18V DC  

load resistance: 600

 or greater

Off voltage: 0.1V DC or less 

short-circuit current: approx. 30mA

(3) Current output
Output signal: 4 to 20mA
Maximum load resistance: 600

Output accuracy: 

±

0.3% of span

                (at 23

±

2

°

C ambient temperature)

Measured Value Input

Alarm Functions

Control Output

The retransmission output is provided only when the /RET option is specified, but is 
not available for the heating/cooling type.

 

Output signal: Measured value in 4-20mA DC

 

Maximum load resistance: 600

 

Output accuracy: 

±

0.3% of span (at 23

±

2

°

C ambient temperature)

Retransmission Output

 

Safety: Compliant with IEC/EN61010-1: 2001, approved by CSA1010, approved by 

UL508.  
Installation category : CAT. II (IEC/EN61010, CSA1010)  Pollution degree : 2 
(IEC/EN61010, CSA1010) 
Measurement category : I (CAT. I : IEC/EN61010) 
Rated measurement input voltage : 10V DC max.(across terminals), 300V AC 
max.(across ground) 
Rated transient overvoltage : 1500V (Note) 
Note : It is a value on the safety standard which is assumed by IEC/EN61010-1 in 
measurement category I, and is not the value which guarantees an apparatus 
performance. 
Caution: This equipment has Measurement category I, therefore do not use the 
equipment for measurements within  measurement categories II, III and IV.

 

EMC standards: Complies with EN61326.

The instrument continues to operate at a measuring accuracy of within

±

20% of the

range during tests.

Safety and EMC Standards

The communication function is provided only when the /RS option is specified. (For details, read the 
user’s manual of the communications function IM 05C01E12-10E.)

Communication Protocol

 

Personal computer link: Used for communication with a personal computer, or UT 

link module of the FA-M3 controller (from Yokogawa Electric Corporation).

 

Ladder communication: Used for communication with a ladder communication 

module of the FA-M3, or a programmable controller of other manufacturers. 

 

MODBUS communication: Used for communication with equipment featuring the MODBUS protocol.  

Communication Interface

 

Applicable standards: Complies with EIA RS-485

 

Number of controllers that can be connected: Up to 31 

 

Maximum communication distance: 1,200m

 

Communication method: Two-wire half-duplex, start-stop synchronization, non-procedural

 

Communication speed: 2400, 4800, or 9600 bps

Communication Function

Alarm Functions (Option Code /AL or /HBA)

 

Alarm types: 22 types (waiting action can be set by software):

PV high limit, PV low limit, Deviation high limit, Deviation low limit, De-energized 
on deviation high limit, De-energized on deviation low limit, Deviation high and low 
limits, High and low limits within deviation, De-energized on PV high limit, De-
energized on PV low limit, Fault diagnosis output, FAIL output

 

Alarm output: 2 relay contacts

Relay contact capacity: 1A at 240V AC or 1A at 30V DC (with resistance load)
Note: The alarm output relays cannot be replaced by users.

Heater Disconnection Alarm (Option Code /HBA)

The heater disconnection alarm is available when time-proportional PID control or 
on/off control is selected.

 

Heater current setting range: 1 to 80A

 

Alarm output: 1 relay contact (The terminals are the same as those of the /AL option.)

 

On time of burn-out detection: Min. 0.2 second

 

Sensor: CTL-6-S-H or CTL-12-S36-8 (URD Co., Ltd.)

To be purchased separately.

Timer Function (Option Code /EX/AL or /EX/HBA)

The output contact status changes when the preset time has passed since external contact (TMR) 
turned on. 
The contact action can be selected by software from: 
(1) Make contact–the contact closes upon time-up.
(2) Break–the contact opens upon time-up.

 

Input contact type: See  

Contact Inputs

 

 below.

Contact Inputs

The contact inputs are provided only when the /EX option is specified. 

 

Functions: (1) Switching over two setpoints (SP1 and SP2)

 

(2) Starting a timer (See the  

Alarm Functions

 

.)

 

(3) RUN/STOP switching

                      Can be selected by parameter DIS.

 

Input: 2 points (with the shared common terminal)

 

Input type: Non-voltage contact or transistor contact input

 

Contact capacity: At least 12V/10mA

 

On/off judgment: On state for 1k

 or less; off state for 20k

 or greater

Internal Wiring

Entrance
Cable

4

3

T

2

1

2

3

4

Measurement  

category

CAT.

1

CAT.

2

CAT.

3

CAT.

4

 

     

 Remarks

Appliances, 
portable equipments, 
etc.

Distribution board, 
circuit breaker, etc.

Overhead wire, 
cable systems, 
etc.

 

 

 

 Description

 

For measurements performed on 
circuits not directly connected to MAINS.

For measurements performed on  
circuits directly connected to the 
low voltage installation.

For measurements performed in  
the building installation.

For measurements performed at 
the source of the low-voltage installation.

Содержание UT150

Страница 1: ...User s Manual Models UT150 UT152 UT155 Temperature Controllers IM 05C01E12 41E IM 05C01E12 41E 2004 6 4th Edition...

Страница 2: ...e both manuals have the same contents except for some minor differences in the cross referenced page numbers Revision Record Manual No IM 05C01E12 41E 4th Edition Title Models UT150 UT152 UT155 Temper...

Страница 3: ...20mA output continuous PID Option AL HBA EX RET RS V24 Alarm outputs 2 points Heater disconnection alarm includes optional AL function SP1 SP2 switching starting of timer and RUN STOP switching by ex...

Страница 4: ...fe The following symbols are used in this manual only NOTE Indicates that operating the hardware or software in a particular manner may lead to damage or result in system failure IMPORTANT Draws atten...

Страница 5: ...ol the left upper lamp lights up in orange when the heating side output is active while the right lower lamp lights up in green when the cooling side output is active g Data change keys Indicated as s...

Страница 6: ...close the controller in shielding panels positioned at least 150mm away from each side These panels should be made of either 1 43mm thick metal plated steel plates or 1 6mm thick uncoated steel plates...

Страница 7: ...T155 N is the number of controllers If N 5 then measure the actual length N 1 96 92 0 8 0 1 1021 301 20 min 70 48 min 145 92 0 8 0 45 0 6 0 max 44 6 max 91 8 max 112 100 96 Panel thickness 1 to 10 11...

Страница 8: ...n the 3 wires See the table given later for the specifications of the cables and terminals and the recommended products 3 The control output relay cannot be replaced even though it has a limited servi...

Страница 9: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TC Input DC mV or V Input RTD Input 7 8 7 8 6 7 8 B b A NO COM ALM2 ALM1 COM Relay Contact Output 4 to 20 mA DC Output Voltage Pulse Output Heating side Control Out...

Страница 10: ...stand for the polarity for DC 24V power supply UT152 UT155 Terminal Arrangement Heating cooling type 11 21 22 23 24 25 26 27 28 29 30 12 13 14 15 16 17 18 19 20 TC Input DC mV or V Input RTD Input 12...

Страница 11: ...tandards The communication function is provided only when the RS option is specified For details read the user s manual of the communications function IM 05C01E12 10E Communication Protocol Personal c...

Страница 12: ...155 For side by side close installation the controller loses its dust proof and drip proof protection Casing ABS resin and polycarbonate Case color Black Mounting Flush panel mounting Power Supply and...

Страница 13: ...2 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 Thermocouple RTD DC voltage K J T E R S B N L U Platinel 2 Pt100 JPt100 0 to 100mV 0 to 5V 1 to 5V 0 to 10V Unspecified 270 to 1370 C 0 0 to 600 0 C 0...

Страница 14: ...n explains how to set and register parameter values The procedure for changing SP target setpoint and A1 alarm 1 setpoint can be found on Changing Target Setpoint SP and Changing Alarm 1 Setpoint A1 r...

Страница 15: ...y for at least 3 seconds If your controller has the AL or HBA option the display for the Alarm 1 setpoint A1 appears If not control mode CTL appears Press for at least 3 seconds Step 3 Press the key o...

Страница 16: ...ONF on off control CTL PID Displayed when I OFF Displayed for heating cooling type Displayed for heating cooling type Displayed for time proportional PID control Displayed for time proportional PID c...

Страница 17: ...ds or hours and minutes Set the timer time unit using parameter TTU For example 15 25 sets 15 minutes and 25 seconds T1 is for AL1 and T2 is for AL2 0 00 T2 Timer setting 2 0 00 2 Operating Parameters...

Страница 18: ...UPER function Note Not displayed when on off control OFF 0 DR Direct reverse action 0 Reverse action 1 Direct action Note Not displayed for heating cooling type 0 ADR Controller address 1 to 99 Howeve...

Страница 19: ...n on Alarm setting Measured value Measured value Temperature setpoint Hysteresis Deviation setting Opn on Cls off The output contact is opened in the following events Program error ROM error RAM error...

Страница 20: ...is function operates at the following events a SP change b SP1 SP2 switching c Power on At power on SP starts from the current PV value Set the ramp rate time unit using parameter TMU The cycle time i...

Страница 21: ...P and then turn the controller off once and then back on again Do not use dynamic auto tune control for a system where there is interference or continual disturbances IMPORTANT To use dynamic auto tun...

Страница 22: ...proper values B o Input burnout Check the sensor wiring and correct it OOO PV over scale PV exceeds its effective range Check the input type and range settings and correct them Press any key to stop...

Страница 23: ......

Страница 24: ...SUL S A Headquarters Plant Praca Acapulco 31 Santo Amaro Sao Paulo SP BRAZIL CEP 04675 190 Phone 55 11 5681 2400 Facsimile 55 11 5681 4434 YOKOGAWA ENGINEERING ASIA PTE LTD Head office 5 Bedok South...

Отзывы: