< 4. SETTING PARAMETERS >
4-7
IM 12E04B40-02EN
1st Edition : Mar. 08, 2023-00
4.3.3
Operating days
Set each counts of parameter enabled/disabled
If you want to confirm the value of operation days, enable the function. However, even if you set it
disabled, the operating day counts internally. TB830D does not use the Wiper operating days.
4.4
Communication setting
n
Sensor connection address
You can change Modbus address. Normally, you do not need to change setup. After changing
Modbus address, you need to change the configuration of the converter that connects to the
system. To change the converter setting, Converter menu > Setting > Converter setting >
Advanced settings > MODBUS setting >Sensor Address setting (S) Refer FLXA402T Operation
of Converter (IM 12A01G01-03EN).
CAUTION
The change in sensor addressing setup is reflected by turning OFF/ON Power Supply.
4.5
Automatic cleaning/Automatic zero
calibration setting
This setup is a converter setup.
4.5.1
Auto sequence for wash/cal.
Enable this function to use Automatic cleaning/Automatic zero calibration.
If this function is disabled, automatic cleaning/automatic zero calibration is never implemented
even if other setting is active.
4.5.2
Start date
First set the date and time to activate automatic cleaning/automatic zero calibration. As the first
time automatic cleaning/automatic zero calibration, enter a future date/time but not the current
one.
If you want to perform the next and subsequent automatic cleaning/automatic zero calibration
automatically, turn ON Auto update of start date. The next date of automatic cleaning/automatic
zero calibration is determined according to the washing interval.
4.5.3
Automatic cleaning/Automatic zero calibration
function and wash type
You can set Automatic cleaning function and Automatic zero calibration function respectively to
Enable/Disable. When you use Auto calibration, always set Automatic cleaning to Enable Always
select water flow as wash type.