<9. TECHNICAL DATA>
9-9
IM 01R01B02-00E-E 12th edition October 01, 2014 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
LIMIT SWITCHES
Intrinsically safe limit switches with ATEX-certifica-
tion (option /K1 ... /K10 with /KS1) :
Certificate:
- PTB 99 ATEX 2219X ( SC3.5-NO)
(/K1 ... /K3)
- PTB 00 ATEX 2049X (SJ 3.5-S.N)
(/K6 ... /K10)
Explosion proof :
Ex ia IIC T6, group II category 2G
Entity parameter :
see certificate of conformity
Intrinsically safe limit switches with ATEX-certifi-
cation for use in category 3G (option /K1 ... /K10
with /KS3) :
Explosion proof :
Ex ic IIC T6 X, group II category 3G
Entity parameter :
see specification of SC3,5-N0 Blue (P&F)* (/K1 ... /K3)
see specification of SJ3,5-SN (P&F)* (/K6 ... /K10)
* P&F = Pepperl & Fuchs
Intrinsically safe limit switches with IECEx-
certification (option /K1 ... /K10 with /ES1) :
Certificate:
-
IECEx PTB11.0091 (SC3.5-NO) (/K1 ... /K3)
-
IECEx PTB11.0092 (SJ 3.5-S.N) (/K6 ... /K10)
Explosion proof :
Ex ia IIC T6 Gb
Entity parameter :
see certificate of conformity
Intrinsically safe / non incendive limit switches
with FM- certification (USA) (option /K1 ... /K10
with /FS1) :
Explosion proof :
IS : Cl.
I, Div. 1, Gp.
ABCD, T6, Ta = 60°C,
Nl : Cl. I, Div. 2, Gp. ABCD, T5, Ta = 50°C
Cl. II, Div. 1, Gp. EFG
Cl. III, Div. 1
Entity parameter :
see FM-control drawing 116-0165 for IS
see FM-control drawing 116-0155 for Nl
Intrinsically safe limit switches with CSA- certifi-
cation (Canada) (option /K1 ... /K3 with /CS1) :
Explosion proof :
Cl.
I, II, III, Div. 1, Gp.
ABCDEFG
Entity parameter :
see drawing 116-0047
Only in combination with option
/WxA or /WxB.
Intrinsically safe limit switches with NEPSI-
certification (China) (option /K1 .. /K10 with /NS1):
Certificate :
GYJ11.1505X (option /K1.../K3)
GYJ11.1507X (option /K6.../K10)
Explosion proof :
Ex ia IIC T1 ... T6
Entity parameter :
see certificate
Intrinsically safe limit switches with EAC-
certification (Russia, Belorussia, Kazakhstan)
(option /K1 .. /K10 with /GS1):
Certificate :
RU С-DЕ.ГБО5.В.00338
Explosion proof :
0Ex ia IIC T16...T1 X
Entity parameter :
see certificate
POWER SUPPLIES FOR INTRINSIC SAFE
COMPONENTS
Power Supply for the intrinsically safe electronic
transmitter (option /UT)
Type :
Power supply with galvanically separated input and output
- RN221N-B1, HART- compatible
Certificate :
ATEX:
PTB 00 ATEX 2018
IECEx:
PTB06.0089
FM:
3007835, Control Drawing 02 02 00 111
CSA:
1067708, Control Drawing 02 02 00 112
NEPSI:
GYJ06495
Supply voltage :
20 ... 250 V DC / AC 50/60 Hz
Maximum load impedance :
700 Ω
Output signal :
4 - 20 mA
Control circuit :
Intrinsically safe [Ex ia] IIC; group II ; category (1)GD
Entity parameters :
see fig. 4
Power supply for intrinsically safe limit switches
(option W__):
Type
:
acc. DIN EN 50227 (NAMUR)
- KFA5-SR2-Ex*-W (115 V AC)
- KFA6-SR2-Ex*-W (230 V AC)
- KFD2-SR2-Ex*-W (24 V DC)
- KHA6-SH-Ex1 (115/230 V AC), Fail Safe, 1 channel
- KFD2-SH-Ex1 (24 V DC), Fail Safe, 1 channel
Certificates :
-
KFA5-SR2-Ex*-W: ATEX
: PTB 00 ATEX 2081
CSA
: 1029981 (LR 36087-19)
FM
: ID 3011578
IECEx : PTB11.0031
PESO
: P333188/1
KOSHA : 2009-BO-0157
-
KFA6-SR2-Ex*-W: ATEX
: PTB 00 ATEX 2081
CSA
: 1029981 (LR 36087-19)
FM
: ID 3011578
IECEx : PTB11.0031
PESO
: P333188/1
KOSHA : 2009-BO-0157
-
KHA6-SH-Ex1:
ATEX
: PTB 00 ATEX 2043
-
KFD2-SR2-Ex*-W: ATEX
: PTB 00 ATEX 2080
CSA
: 1029981 (LR 36087-19)
FM
: ID 3011578
IECEx : PTB11.0034
PESO
: P333188/2
KOSHA : 2009-BO-0157
NEPSI : GYJ12.1081
-
KFD2-SH-Ex1:
ATEX
: PTB 00 ATEX 2042
NEPSI : GYJ091350
Control circuit (ATEX)
:
[Ex ia] IIC; group II ; category (1)GD
Entity parameter
:
see fig. 4
(
ATEX) and certificate