<7. HART-COMMUNICATION>
7-7
IM 01R01B02-00E-E 12th edition October 01, 2014 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
7.4.1 Process variables
Device setup
Process variables
Flow value [cum/h]
Flow in oriented measurement unit
Flow % rnge [%]
%-value related to 20mA
Flow AO value [mA]
Current output in mA
Totalizer value [kg]
Totalizer
% span value
%-Value related to flow final value
Temperature value [°C]
Temperature in transmitter
7.4.2 Diagnostic- and Service-Menu
Device setup
Diag/Service
Test
device
Device
status
Status group 1
Error
indication:
RAM Error
OFF/ON Memory error
ADC Error
OFF/ON error A/D converter
ADJ-EE-Error
OFF/ON error adjustment-EEPROM
CAL-EE Error
OFF/ON error calibration-EEPROM
Totalizer false
OFF/ON totalizer value false
Flow Overrun
OFF/ON Flow too high
ADJ Error 2
OFF/ON adjustment-EEPROM fault
Float blocked
OFF/ON Float-Move-Detection recognized, supervision
time
passed
Device setup
Diag/Service
Test
device
Device
Status
Status group 2
Error
indication:
Temp over limit
OFF/ON Temperature exceed 70°C
Max flow1 active
OFF/ON URV overrun
Max flow2 active
OFF/ON URV underrun
FB autoz active
OFF/ON Float blocking autozero on
Power fail warn
OFF/ON Power off has happened
Oper timer error
OFF/ON Operation timer fault
Mancal active
OFF/ON Manual calibration activated