A4-1
IM 34M06C11-01E
A4.
Test Runs and Troubleshooting
A4.1
Test Run Procedure
Figure A4.1 shows the test run flowchart.
Wiring check before power-on
Insulation and withstanding
voltage test
Supply voltage measurement
Power-on test
External wiring check
Safety circuit check
Individual-mode
operation
Automatic operation
Fault-simulating
operation
•••
•••
•••
•••
•••
•••
•••
•••
•••
•••
Te
st r
un
Installation check
Check the construction of the control panel and the FA-M3
installation. Check the installation of the individual modules.
Check cables to ensure that all cables are properly routed and
connected to meet the wiring specifications.
The FA-M3 is a delicate electronic device. Special care must be taken
to avoid damage to the device when checking the insulation of the
machine or facility that uses this device.
Before turning on the power, measure the supply voltage to ensure
that it conforms to the given specifications.
There are two ways to check the external wiring: by using a multimeter
to examine the cables one at a time, or by actually turning the power
on and looking for problems. The latter method may be hazardous for
safety reasons and, therefore, require adequate care.
Start the test by checking the operation of safety circuits such as
emergency-stop circuits and protective circuits which are actuated
when the device gets into trouble.
Test each operating mode by stepping through the machine or facility
with push buttons.
Run each of specific blocks of the machine or facility in the automatic
mode or run a standalone test on the machine or facility in the
automatic mode. Then, proceed to full automatic operation of the
entire system.
Test to make sure that safety circuits actuates and reset normally
when anomalies occur in the machine or facility.
Before turning on the power, take all possible measures to minimize
any damage that might result from faulty wiring. Then, turn the power
on and check for problems.
FA040101.VSD
P
relim
inar
y
c
hec
k
Figure A4.1 Test Run Flowchart
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...