A3-44
IM 34M06C11-01E
To external
equipment
FG clamp
Shielded cable
To networks
HUB
Remove part of the insulation of a
shielded cable and ground the
exposed shield to the metal plate of
the panel enclosure using
an FG clamp.
Ensure that Ethernet,
DeviceNet, GP-IB and
other cables leading out
of the panel enclosure for
connection to external
equipment are shielded
cables and their shield is
grounded using FG
clamps.
Pig-tail grounding does
not provide sufficient
grounding.
Minimize cable
wiring.
Fitting ferrite cores on I/O cables is
expected to improve EMC performance.
Ferrite core, if fitted, should be near the
opening of the panel enclosure.
Route cables away from
noise sources.
Noise filter
Route wires before and after
the filter apart.
Power-motive
cable of motors,
etc.
FA030904.VSD
Fit ferrite cores on power
cables of YHLS slave units
(TAH series), F3PU30-0S and
F3PU36-0S.
Figure A3.38 Example of Routing Measures
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...