7-42
IM 34M6H55-02E
1st Edition : Apr 1, 2002-00
z
z
z
z
Conditions for Command Execution:
- The axis is not in an error state.
- The axis is in the End-of-Positioning status.
- No other command is being executed.
z
z
z
z
Note:
- If any of the conditions is not satisfied, the command is ignored and the Command
Execution ACK relay is not set. If the command is issued when the axis is in an
error state or not in the End-of-Positioning status, an alarm code is set in the alarm
status. The alarm code is automatically cleared when the Execute Command
output relay is reset. For details on alarm codes, see Section 8.3, “Alarm Codes.”
- The origin search ends when a specified external contact input is detected and the
axis is stopped. Change the parameters and begin the origin search again if you
wish to continue the search in another direction or at a different speed.
- In the following cases, an error occurs and the origin search is aborted:
- The limit input of the origin-search direction is set to be ignored but is detected.
- After shifting to Z-phase search, the limit switch of the origin search direction is
detected (this always causes an error regardless of the setting).
- After shifting to Z-phase search, no Z-phase pulse is detected within the origin
search Z-phase search range.
- If you wish to change the setup values according to the state of the external contact
input at the beginning of the origin search, read the state with the Contact Input
Status before executing the origin search.
- After shifting to Z-phase search, even if the external contact input that sets the Stop
Immediately or Decelerate and Stop operation is detected, the Z-search operation
will continue. (This is different from an origin search in the F3NC11-0N and
F3NC12-0N modules)
- During the origin search, even if the axis exceeds the range defined by the positive
and negative direction limit values, no error occurs.
z
z
z
z
Procedure:
1
.
Write the entry and command parameters required for the origin search operation to
the positioning module with the OUTPUT instruction (set the command code to 2).
2
.
Set the Execute Command output relay. The Execute Command ACK input relay
will be set and the automatic origin search begins. Operation continues until the
specified external contact input is detected. If there is an invalid parameter, the Error
Notification Input Relay will be set but not the Execute Command ACK Input Relay.
3
.
When Z-phase pulses are detected for the specified number of times after shifting
to Z-phase search (if this number is specified as ‘’0," the module skips the
Z-phase search), the current position is specified as “Position 0” and the axis stops
immediately. After outputting the deviation pulse clear signal for a preset duration,
the End of Positioning input relay is set.
4
.
Confirm the state of origin search by checking the origin search status. If the origin
search status is “0,” the origin search has ended following a successful
Z-phase search. For details on the origin search status, see Section 5.2,
“Description of Statuses”.
Содержание F3YP14-0N
Страница 13: ...Blank Page ...
Страница 15: ...Blank Page ...
Страница 23: ...Blank Page ...
Страница 53: ...Blank Page ...
Страница 60: ...7 5 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 2 Set Parameter Program ...
Страница 65: ...7 10 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 6 Jog Stepping Program ...
Страница 69: ...7 14 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 9 Origin Search Program ...
Страница 77: ...7 22 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 15 Positioning Operation Program ...
Страница 111: ...Blank Page ...
Страница 127: ...Blank Page ...