8.3 Alarm
Codes
When the positioning module issues an alarm for any axis, it writes an alarm code in the
Alarm Status for the axis. An alarm is issued when an executed command does not
meet the conditions for proper execution. Resetting the Execute Command relay or
other output relay related to the invalid command clears the Alarm Status.
The following table lists the types of alarm detectable by the positioning module.
Table 8.2 Alarm Codes
Alarm Code
Type of Alarm
Cause of Alarm
1001 Start
Positioning
Command Failed alarm
Start Positioning Command is executed in an error state.
1002 Start
Positioning
Command Failed alarm
Start Positioning Command is executed when the axis is not
in an End of Positioning state.
1101 Decelerate-and-Stop
Command Failed alarm
Decelerate-and-Stop Command is executed in an error state.
1103 Decelerate-and-Stop
Command Failed alarm
Decelerate-and-Stop Command is executed during a jog
stepping operation.
1201
Origin Search Command
Failed alarm
Normal Origin Search Command is executed in an error
state.
1202
Origin Search Command
Failed alarm
Normal Origin Search Command is executed when the axis
is not in an End of Positioning state.
1302 Set
Parameter
Command Failed alarm
Set Parameter Command is executed when the axis is not in
an End of Positioning state.
1401
Set Current Position
Command Failed alarm
Set Current Position Command is executed in an error state.
1402
Set Current Position
Command Failed alarm
Set Current Position Command is executed when the axis is
not in an End of Positioning state.
1501
Reset Error Command
Failed alarm
Reset Error Command is executed when no error exists or
when a parameter setting error exists.
1601 Change
Speed
Command Failed alarm
Change Speed Command is executed in an error state.
1602 Change
Speed
Command Failed alarm
Change Speed Command is executed when the axis in the
End of Positioning status.
1604 Change
Speed
Command Failed alarm
Change Speed Command is executed during an origin
search.
1605 Change
Speed
Command Failed alarm
Change Speed Command is executed when the axis is
accelerating (not including jog stepping), decelerating, or
already changing its speed (not including jog stepping).
1606 Change
Speed
Command Failed alarm
Executing the Change Speed Command will prevent the axis
from stopping at the target position.
1607 Change
Speed
Command Failed alarm
Change Speed Command is executed when the axis is
changing its target position.
1701 Change
Target
Position
Command Failed alarm
Change Target Position Command is executed in an error
state.
1703 Change
Target
Position
Command Failed alarm
Change Target Position Command is executed during jog
stepping.
1704 Change
Target
Position
Command Failed alarm
Change Target Position Command is executed during origin
search.
1707 Change
Target
Position
Command Failed alarm
Change Target Position Command is executed when the axis
is already changing its target position.
1801
Automatic Origin Search
Command Failed alarm
Automatic Origin Search Command is executed in an error
state.
1802
Automatic Origin Search
Command Failed alarm
Automatic Origin Search Command is executed when the
axis is not in an End of Positioning state.
1901 Save
Parameter
Command Failed alarm
Save Parameter Command is executed in an error state.
1902 Save
Parameter
Command Failed alarm
Save Parameter Command is executed when the axis is not
in an End of Positioning state.
2001
Jog Stepping Command
Failed alarm
Jog Stepping Command is executed in an error state.
2002
Jog Stepping Command
Failed alarm
Jog Stepping Command is executed when the axis is not in
an End of Positioning state.
2101 Stop
Immediately
Command Failed alarm
Stop Immediately Command is executed in an error state.
Содержание F3YP14-0N
Страница 13: ...Blank Page ...
Страница 15: ...Blank Page ...
Страница 23: ...Blank Page ...
Страница 53: ...Blank Page ...
Страница 60: ...7 5 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 2 Set Parameter Program ...
Страница 65: ...7 10 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 6 Jog Stepping Program ...
Страница 69: ...7 14 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 9 Origin Search Program ...
Страница 77: ...7 22 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 15 Positioning Operation Program ...
Страница 111: ...Blank Page ...
Страница 127: ...Blank Page ...