![YOKOGAWA F3YP14-0N Скачать руководство пользователя страница 83](http://html1.mh-extra.com/html/yokogawa/f3yp14-0n/f3yp14-0n_user-manual_910940083.webp)
7-28
IM 34M6H55-02E
1st Edition : Apr 1, 2002-00
7.1.11 Changing Speed during Operation
When the Change Speed command is issued during a positioning operation, the axis
immediately starts to accelerate (or decelerate) to the new speed at a rate determined
by the new speed and the acceleration (or deceleration) time. When the axis
subsequently decelerates and stops from the new target speed to complete the
positioning operation, or when the Decelerate-and-Stop command is issued, the
deceleration rate is determined by the new speed and the deceleration time.
z
z
z
z
Conditions for Command Execution:
- The axis is not in an error state.
- The axis is not in the End-of-Positioning status.
- The axis is not executing an origin search operation.
- The axis is not accelerating in a positioning operation.
- The axis is not decelerating in a positioning operation or in a jog stepping operation.
- The axis is not changing its target speed in a positioning operation.
- The axis can stop at the target position even after changing to the new speed.
- The axis is not changing its target position.
z
z
z
z
Note:
- If any of the conditions is not satisfied, the command is ignored and the Command
Execution ACK relay is not set.
If the command is issued but not all the conditions are satisfied, an alarm code is
set in the alarm status. The alarm code is automatically cleared when the Execute
Command output relay is reset. For details on alarm codes, see Section 8.3,
“Alarm Codes.”
- If the Change Speed command is issued during a jog stepping operation, the
module waits until all acceleration and deceleration has been completed before
executing the command. If a new Change Speed command is issued during the
wait, the previous command is discarded and only the new command is executed.
- If a command parameter is invalid, an error occurs and the axis stops immediately.
z
z
z
z
Procedure:
1
.
Write the required parameters and command code to the positioning module with
the WRITE instruction or any other appropriate instruction (set the command code
to 6).
2
.
Set the Execute Command output relay.
3
.
The Execute Command ACK input relay is set, and the Change Speed operation
starts. Reset the Execute Command output relay after confirming that the Execute
Command ACK input relay is set. If there is an invalid parameter, the Error
Notification input relay will be set, but the Execute Command ACK input relay will
not be set.
4
.
Confirm that the Execute Command ACK input relay is reset.
Содержание F3YP14-0N
Страница 13: ...Blank Page ...
Страница 15: ...Blank Page ...
Страница 23: ...Blank Page ...
Страница 53: ...Blank Page ...
Страница 60: ...7 5 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 2 Set Parameter Program ...
Страница 65: ...7 10 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 6 Jog Stepping Program ...
Страница 69: ...7 14 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 9 Origin Search Program ...
Страница 77: ...7 22 IM 34M6H55 02E 1st Edition Apr 1 2002 00 Figure 7 15 Positioning Operation Program ...
Страница 111: ...Blank Page ...