3-10
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
■
Grounding the Communication Cables
For better signal noise immunity, it is recommended to connect either end of the
cable shield at the SHIELD terminal (both-end grounding method).
*1
(If many power
machines are used near the modules and grounded locally, however, use the single-
end grounding method to protect against noise from stray current.)
F3LP32-0N
Remove the cove r
and secure with an
FG clamp.
Shie lded cable
Screw the
clamp to th e
metal p late of
the panel
enclosure to
grou nd it.
Figure 3.6.4 Grounding the Communication Cable
*1: To conform the equipment incorporating this module to CE marking, use shielded cables.
In addition, remove the cable covering to expose the shield, and then ground and
secure it using an FG clamp.
■
Setting terminating resistors
F3LP32-0N has an in-built termination resistor (110Ω). FA Link modules on both
ends of the transmission path must have their Termination Resister ON/OFF switch
set to ON (See Figure 3.6.5).
FA Link modules not located at either end of the transmission path must have this
switch set to OFF.
0
0
LP32-0N FA LINK
LNK
Terminator switch (TERMINATOR):
ON :
Terminator is enabled.
OFF:
Terminator disabled.
The factory setting is OFF.
Figure 3.6.5 Terminating Resistor ON/OFF
Содержание F3LP32-0N
Страница 2: ...Blank Page...
Страница 14: ...Blank Page...
Страница 18: ...Blank Page...
Страница 24: ...Blank Page...
Страница 36: ...Blank Page...
Страница 82: ...Blank Page...
Страница 92: ...Blank Page...
Страница 100: ...Blank Page...
Страница 102: ...Blank Page...
Страница 104: ...Blank Page...