4-6
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
4.2 Response Time of a Single Layer System
Use the equations below to obtain the following components of the response
time:
- Scan time of the sequence program in the transmitting and receiving
stations
- Link refresh processing time in the transmitting and receiving stations
- Cyclic transmission processing time
■
For Normal Mode
(1)
Maximum response time of a single layer system (T
LD
)
T
LD
= ST
S
+ LR
S
2 + CT
3 + (ST
R
2) + (LR
R
2) + IM (unit: ms)
where,
ST
S
= Sequence program scan time of transmitting station
LR
S
= Link refresh time of transmitting station
CT = Cyclic transmission time
ST
R
= Sequence program scan time of transmitting station
LR
R
= Link refresh time of receiving station
IM = Internal processing time (constant: 50 ms)
Note:
The internal processing time of high-speed mode is 30 ms.
(2)
Link Refresh Time (LR)
LR = (RL
L
/16+RG
L
)
0.012
1.2 (unit: ms)
where,
RL
L
= Number of link relays used in the station
RG
L
= Number of link registers used in the station
(3)
Cyclic Transmission Time (CT)
CT = (RL
A
+ RG
A
16 + 200
S)
BT + 1.3
S + 8 (unit: ms)
where
RL
A
= Total number of link relays used in all stations
RG
A
= Total number of link registers used in all stations
BT = Transmission time per bit
BT = 0.0008 (1.25Mbps)
BT = 0.0016 (625kbps)
BT = 0.004 (250kbps)
BT = 0.008 (125kbps)
S = Total number of connected stations
Содержание F3LP32-0N
Страница 2: ...Blank Page...
Страница 14: ...Blank Page...
Страница 18: ...Blank Page...
Страница 24: ...Blank Page...
Страница 36: ...Blank Page...
Страница 82: ...Blank Page...
Страница 92: ...Blank Page...
Страница 100: ...Blank Page...
Страница 102: ...Blank Page...
Страница 104: ...Blank Page...