< PART – B Software >
B-123
IM 39J06B40-01EN
14th Edition: May 30, 2022
●
Temperature Rise Limit
Specify a temperature rise limit value from 0.00 to 1273.14.
An alarm is reported when (measured value – previous measured value) exceeds the
limit.
Specify a value n from 1 to 10 to use the nth preceding measured value as the previous
measured value for comparison.
The alarm mode setting is enabled.
●
Temperature Fall Limit
Specify a temperature fall limit value from 0.00 to 1273.14.
An alarm is reported when (previous measured value – measured value) exceeds the
limit.
Specify a value n from 1 to 10 to use the nth preceding measured value as the previous
measured value for comparison.
The alarm mode setting is enabled.
●
Temperature Difference Limit
Specify a temperature difference limit from 0.00 to 1273.14.
An alarm is reported when the difference between the maximum and minimum
measured values within a section exceeds the limit.
The alarm mode setting is disabled.
●
Delay Temperature High Limit
Specify a delay temperature high limit value from -273.15 to 999.99.
An alarm is reported when the measured value exceeds the limit for a specified number
of successive measurements.
The alarm mode setting is enabled.
Specify the number of successive measurements as a value from 1 to 10.
●
Delay Temperature Low Limit
Specify a delay temperature low limit value from -273.15 to 999.99.
An alarm is reported when the measured value is below the limit for a specified number
of successive measurements.
The alarm mode setting is enabled.
Specify the number of successive measurements as a value from 1 to 10.
●
Temperature Difference High Limit
Specify a temperature difference high limit value from 0.00 to 1273.14.
An alarm is reported when the difference between the average value and each
measured value within a section exceeds the limit.
The alarm mode setting is disabled.
●
Temperature Difference Low Limit
Specify a temperature difference low limit value from 0.00 to 1273.14.
An alarm is reported when the difference between the average value and each
measured value within a section is below the limit.
The alarm mode setting is disabled.
Содержание DTSXL
Страница 2: ...Blank Page...
Страница 15: ...Copyright and Trademark Notices xiii IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 23: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 83: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 215: ...PART B Software B 132 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 222: ...PART B Software B 139 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 233: ...PART B Software B 150 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 239: ...PART B Software B 156 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 247: ...PART B Software B 164 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 253: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 289: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...