< PART – B Software >
B-122
IM 39J06B40-01EN
14th Edition: May 30, 2022
There are 9 available alarm types, which can be enabled or disabled individually for
individual alarm sections. All alarm limit values can be specified with a resolution of 0.01
[deg C].
You can select either of the following alarm modes for some alarm types:
- Select Point to report an alarm when any measured value within the section
satisfies the alarm condition.
- Select Average to report an alarm when the average measured value of a section
satisfies the alarm condition.
●
Temperature High Limit
Specify a temperature high limit value from -273.15 to 999.99.
An alarm is reported when the measured value exceeds the limit.
The alarm mode setting is enabled.
●
Temperature Low Limit
Specify a temperature low limit value from -273.15 to 999.99.
An alarm is reported when the measured value is below the limit.
The alarm mode setting is enabled.
Содержание DTSXL
Страница 2: ...Blank Page...
Страница 15: ...Copyright and Trademark Notices xiii IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 23: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 83: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 215: ...PART B Software B 132 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 222: ...PART B Software B 139 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 233: ...PART B Software B 150 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 239: ...PART B Software B 156 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 247: ...PART B Software B 164 IM 39J06B40 01EN 14th Edition May 30 2022...
Страница 253: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...
Страница 289: ...IM 39J06B40 01EN 14th Edition May 30 2022 Blank Page...