24
IM XL120P
7.
Signal Wiring
Signal Input Wiring (for Clamp Screws)
Be sure to also read the precautions in section 3.3, “Wiring the Input Signal
Cable” in the User’s Manual when wiring cables.
CAUTION
Do not apply an input exceeding the following values. Otherwise, the XL100
may break down.
• Maximum input voltage
100 mV, 500 mV, and 1 V range and TC input:
±
10 VDC
5 V, 10 V, 50 V, and 1-5V/f.s. range:
±
60 VDC
• Maximum common mode noise voltage
30 VACrms (50/60 Hz) or
±
60 VDC
Wiring Procedure
1.
Open the terminal cover of the terminal block unit.
2.
Wire the input signal cables to the input terminals.
As shown below, loosen the terminal screws using the screwdriver provided,
insert the signal wires, and fasten the terminal screws.
3.
Close the terminal cover of the terminal block unit.
Enlarged view
Accessory screwdriver
for terminals
Signal wire
Terminal cover
Terminal block unit
TIP
The terminal block unit can be removed. For the procedure to remove the terminal
block unit, see section 3.3, “Wiring the Input Signal Cable” in the User’s Manual.