measurement is plotted. The line graph fully overwrites the old data every 200 seconds (approx. 

3.5 minutes) and will begin again from the left side of the graph. 

 

Operating the Pressure Rise Test: 

The pressure rise test can be accessed through 

completion of an evacuation (See page 13). Once 

the evacuation has been completed, the device 

prompts the user to conduct a pressure hold test. 

If the button is selected, the user will be brought 

to the pressure rise test setup screen shown in 

Figure 27. The pressure rise setup screen allows 

the user to adjust the allowable vacuum pressure 

(allowable change) and test duration.  

 

Allowable change sets the maximum allowable system vacuum pressure above which the P51-

870 TITAN® will indicate a failure. Tap and drag the slider bar to adjust the allowable vacuum 

pressure until the desired value is displayed. The test duration sets the length of time the 

pressure rise test will be conducted. If the system vacuum pressure has not risen above the limit 

pressure within the test duration, the P51-870 TITAN® deems the pressure rise test a pass. Tap 

the + and – buttons to adjust the test duration value. When all desired settings have been set, 

select the continue button to advance to the pressure rise test. The back button can be used to 

return to the previous evacuation screen. 

 

After selecting the continue button, the pressure rise test commences immediately setting the 

current vacuum pressure as the initial system pressure. During the pressure rise test, current 

system vacuum pressure (Pvac) will be monitored and compared to the limit pressure (Set by 

allowable change). The session timer will continue to increment from the previous evacuation 

through the pressure rise test. The percent change per minute (%/min) will display the change in 

system vacuum pressure every minute. A large %/min value indicates a rapid change in pressure, 

conversely small value indicates a small fluctuation in vacuum pressure. The test duration timer 

will continue to deplete until the pressure rise test is complete.  

 

If Pvac rises above the limit pressure within the time limit set by test duration, the device will 

indicate a “FAIL” and the buzzer will sound (Figure 28). To silence the buzzer, exit the pressure 

rise test by selecting the modes menu button. If test duration timer fully depletes before Pvac 

rises above the limit pressure, the device will indicate a “PASS” and the buzzer will sound to 

indicate the test is complete (Figure 29). 

Figure 27: Pressure Rise Setup Menu 

Содержание 40870

Страница 1: ...ese Instructions do not cover the manifold attached to the instrument For instructions on use of the TITAN 4 Valve Manifold please visit https yellowjacket com product titan 4 valve test and charging...

Страница 2: ...des Menu 9 Pressure Temperature Mode 9 Overview 9 Interpreting the Pressure Analog Gauges 10 Interpreting the Pressure and Temperature Line Graphs 10 Operating Pressure Temperature Mode 11 Evacuation...

Страница 3: ...e Units 22 Temperature Units 22 Vacuum Units 22 Device Settings Menu 22 Brightness 22 Backlight Timer 22 Auto Off 23 Logging Rate 23 Ch 5 YJACK View App Integration 24 Overview 24 Operation of the YJA...

Страница 4: ...oid personal injury or death follow these guidelines Most governments and legal authorities re quire that HVAC technicians be trained and certified in the safe and proper operation of HVAC tools such...

Страница 5: ...damaged thermocouple or vacuum sensor could allow an electrical path across the instrument and over wet hoses Keep all interconnected equipment clean organized and in proper condition Do not use the i...

Страница 6: ...and release the power button located at bottom center of the display The YJ logo will appear briefly on startup The current firmware version and Serial Number are displayed at the bottom left and righ...

Страница 7: ...tions on touchscreen calibration see page 21 Connecting and Using the Temperature Clamps Two 67010 temperature clamps pictured in Figure 6 are supplied with the P51 870 TITAN and can be used to monito...

Страница 8: ...distance from the vacuum pump such that it does not disturb the vacuum measurements Interpreting the Battery Life Indicator This instrument utilizes a 2000mAhr rechargeable lithium ion battery It is e...

Страница 9: ...s equipped with an adjustable backlight and backlight auto dimming capabilities When the backlight dims during use a touch anywhere on the screen or a quick press of the power button can be used to wa...

Страница 10: ...nvention preventing duplicates See Figure 15 for example of stored datalog files Ex 50th week of 2017 with device serial number ending in 127 4th datalog file 750127AD These files cannot be modified w...

Страница 11: ...to a larger time increment the LED will not flash blue as often Flashing Red When the device reaches low charge or falls below 10 battery charge the LED will flash red every time a datalog sample is...

Страница 12: ...icon in the upper right hand corner Pressure Temperature Mode Overview The P51 870 TITAN Pressure Temperature mode can be used to accurately diagnose and service any system with compatible refrigerant...

Страница 13: ...s displayed in a digital format at the center of each blue and red analog gauge respectively Each gauge needle adjusts in real time and can be used to observe fluctuations in pressure as if utilizing...

Страница 14: ...e at any time by tapping anywhere within the graph Operating Pressure Temperature Mode While on any modes screen or the modes menu tap the settings icon in the upper right hand corner to access the ge...

Страница 15: ...l Settings Button System vacuum pressure is displayed in real time as a digital representation as denoted by Pvac analog as represented by the green analog gauge and a graphical format as a logarithmi...

Страница 16: ...ding Use the Target and Hold buttons to set the target vacuum level and vacuum hold timer respectively Pressing each of these buttons will cycle between a range of available values with the last value...

Страница 17: ...igerant and non condensables can cause the vacuum level to rise in a system giving a false positive during a leak test when no leak is present Pressure Hold Mode Pressure Decay Test Overview The P51 8...

Страница 18: ...ear scale with minor divisions displayed as small dots and major divisions displayed as larger dots respectively The current system pressure is displayed in a digital format at the center of the analo...

Страница 19: ...s measured as a percent of the initial system pressure the system can drop before the P51 870 TITAN deems the pressure decay test a failure To adjust the allowable change percent drag the slider bar u...

Страница 20: ...will display a FAIL notice Figure 24 and the buzzer will sound indicating the test is complete To silence the buzzer exit the pressure decay test by selecting the modes button If the pressure decay t...

Страница 21: ...gital analog vacuum gauge as evacuation mode The pressure rise gauge operates on a logarithmic scale from atmosphere ATM to 0 microns A digital reading and currently selected vacuum units are displaye...

Страница 22: ...desired settings have been set select the continue button to advance to the pressure rise test The back button can be used to return to the previous evacuation screen After selecting the continue but...

Страница 23: ...gs menus tap on the appropriate button The exit button in the bottom left corner can be used to return to the previous screen at any time Zeroing the Pressure Transducers To ensure accurate pressure r...

Страница 24: ...rigerant Settings Menu The refrigerant settings menu shown in Figure 31 can be accessed either by tapping on the Change Refrigerant button in the general settings menu or by tapping the button in the...

Страница 25: ...the Device Settings button in the general settings menu To adjust the display brightness tap and drag the slider bar next to brightness until the desired brightness is displayed To adjust the backligh...

Страница 26: ...t the logging rate to the lowest possible time interval 1s but this may result in extremely large datalog files making it difficult to analyze the information Be sure to set the logging rate to an app...

Страница 27: ...ce Navigate to the YJACK VIEW App and make sure the manifold is powered on The P51 870 TITAN should appear in the available devices menu as the name of the device followed by the serial number Ex YJP5...

Страница 28: ...dirty generously soak a soft cloth with warm soapy dish soap water and place the cloth for a couple of minutes over the display to loosen any stubborn dirt Wipe off excess water with a clean less damp...

Страница 29: ...acklight Size Approx 7 5 x 8 5 x 4 25 Weight 2 63 lbs Table 7 2 Instrument Specifications Working Pressure 0 700 psia 48 3 bar Pressure Sensing Resolution 0 1 psi 0 1 bar 1 kPa 0 001 MPa 0 01 kg cm 2...

Страница 30: ...d Temperature clamp cable damaged Call technical support Temperature clamp jacks damaged Call technical support Clamp not properly attached to system Check clamp connections to system Low Side and Hig...

Страница 31: ...28...

Отзывы: