68
VS-616PS5 Installation & Quick Start Manual
OPE07
Multi-function analog
input selection fault
(OPE07)
C-option is A1-14B and option/inverter
change is selected.
Check and set the constant
data.
D
OPE08
Multi-function input/
output selection fault
(OPE08)
Any of the following setting faults has
occurred:
• The setting unused in the control method is
selected for F4-01 and F4-04.
• The setting unused in the control method is
selected for F5-01 and F4-02.
• The setting unused in the control method is
selected for H1-01 and H1-06.
• The setting unused in the control method is
selected for H2-01 and H2-03.
• The setting unused in the control method is
selected for H3-05 and H3-09.
• The setting unused in the control method is
selected for H4-01 and H4-04.
• The setting unused in the control method is
selected for o1-01.
Check and set the constant
data.
D
OPE0 10
R/min setting fault
(OPE10)
The settings of E1-06 to E1-08 do not satisfy
the following conditions:
E1-06 E1-07 E1-08
Check and set the constant
data.
D
OPE0 12
Energy-saving control
constants setting fault
Energy-saving control constant values are out
of range.
Check and set the constant
data.
D
OPR
Digital operator fault
(OPr)
The digital operator was disconnected during
operation by run command from the digital
operator.
• Check the wiring cable and the
digital operator connection.
• Replace the control card.
A
ERR
EEPROM R/W
Err
EEPROM writing fault
(ERR)
EEPROM internal data did not match when
initializing the parameter.
Replace the control board.
B
CPF00
COM-ERR
(OP&INV)
Control circuit fault 1
(CPF00)
Digital operator trans-
mission fault
Transmission between the inverter and digital
operator cannot be established 5 seconds
after supplying power.
MPU peripheral element check fault (on-line)
Insert the operator connector
again.
Check the wiring of control cir-
cuit.
Replace the control board.
A
CPF01
COM-ERR
(OP&INV)
Control circuit fault 2
(CPF01)
Digital operator trans-
mission fault
Transmission between the inverter and digital
operator is established once after supplying
power, but later transmission is interrupted for
more than 2 seconds.
MPU peripheral element check fault (on-line).
Insert the digital operator con-
nector again.
Check the digital control circuit
wiring.
Replace the control board.
A
CPF02
BB Circuit Err
Base block circuit fault
(CPF02)
Inverter PCB control board fault.
Replace the control board.
A
CPF03
EEPROM Error
EEPROM fault
(CPF03)
CPF04
Internal A/D Err
CPU internal A/D con-
verter fault (CPF04)
CPF05
External A/D Err
CPU external A/D con-
verter fault (CPF05)
Fault Display
Name
Description
Corrective Action
Class