VS-616PS5 Installation & Quick Start Manual
53
H2 – 01 to H2 – 03
Digital Outputs
Default assignments are as follows:
Listed below are other settings for the digital outputs:
Consult the VS-616PS5 Programming Manual for more settings and more comprehensive descriptions.
H3 – 01 to H3 – 03
Analog Input 1
These parameters set up Analog input 1 (Terminal 13), with terminal 17 common
Consult the VS-616PS5 Programming Manual for the setup of Analog Input 2 and Analog Input 3.
H4 – 01 to H4 – 07
Analog Outputs
These parameters set up Analog input 1, with terminal 17 common
Consult the VS-616PS5 Programming Manual for further information on the Analog Outputs.
Output
Terminals
Parameter
Default
Setting
Default Function
9 – 10
H2-01
0
RUN output – closes while inverter is running
25 – 27
H2-02
1
Zero Speed output – closes while output speed is less than E1-09
26 - 27
H2-03
2
Up to Speed – closes when set speed is attained within tolerance (L4-02)
Setting
Function
3
Speed Match
Speed Matches Setting – closes when output speed = L4-01 +/- L4-02
4
Speed Low
Speed Below setting – closes while output speed < L4-01
5
Speed High
Speed Above Setting – closes while output speed > L4-01
6
Inverter Ready
Ready to Run – closes when inverter has no faults or alarms
7
DC Bus Undervoltage
Closes when DC Bus level or power supply is below trip level
8
Baseblock 1
Closes when inverter output is disabled by a Baseblock command
9
Speed from Operator
Closes while the speed reference is supplied from the digital operator
A
Control from Operator
Closes when the RUN command comes from the digital operator
B
Over Torque Detection
Closes when torque output exceeds setting
C
Reference Loss
Closes when speed reference drops 90% in less than 400 ms
D
DBR Overheat
Closes while Dynamic Braking resistor is overheated or on DB fault
E
Fault
Closes when a fault occurs
F
No Operation
Output is not being used
Parameter
Function
Units
Range
Default
H3-01
Terminal 13 Signal 0: 0 to 10 VDC 1: +/-10 VDC
- -
0/1
0
H3-02
Terminal 13 Reference % Gain
%
0.0 – 1000.0
100.0
H3-03
Terminal 13 Ref/- Bias
%
+/-100.0
0.0
Parameter
Description
Units
Range
Default
Default Function
H4-01
Terminal 21 Analog Output Signal
- -
0…53
5
Motor Speed
H4-02
Terminal 21 Output Gain
- -
0.00 – 2.50
1.00
Gain = 1
H4-03
Terminal 21 Output Bias
%
0.0 – 10.0
0.0
Bias = 0
H4-04
Terminal 23 Analog Output Signal
- -
0…53
3
Output Current
H4-05
Terminal 23 Output Gain
- -
0.0 – 1000.0
1.00
Gain = 1
H4-06
Terminal 23 Output Bias
%
0.0 – 10.0
0.0
Bias = 0
H4-07
Output Signal Selection (both)
- -
0/1
0
0 – 10 VDC