50
VS-616PS5 Installation & Quick Start Manual
Reference Limits
D2 – 01
Reference Upper Limit
Sets the maximum reference as a percent of maximum speed, E7-06.
D2 – 02
Reference Lower Limit
Sets the minimum reference as a percent of maximum speed as entered in E1-06.
PG Option Set-up
F1 – 02
Disconnection Detection Stopping Method
Selects the stopping method when a disconnected PG is detected.
F1 – 03
Overspeed Detection Stopping Method
Selects the stopping method when an overspeed condition is detected.
F1 – 04
Deviation Detection Stopping Method
Selects the stopping method when excessive speed deviation is detected.
Minimum
Maximum Description
Default Setting
000.0
110.0
Speed Reference Upper Limit
100.0
Minimum
Maximum Description
Default Setting
000.0
100.0
Speed Reference Upper Limit
100.0
Setting
Description
0
Ramp to stop - according to C1-02. (Declaration time 1)
1
Coast to stop
(factory default).
2
Fast - stop - according to C1-09.
3
Alarm flashes, operation continues.
Setting
Description
0
Ramp to stop - according to C1-02 (Declaration time 1).
1
Coast to stop
(factory default)
.
2
Fast-stop - according to C1-09.
3
Alarm flashes, operation continues. (
Setting
Description
0
Ramp to stop - according to C1-02 (Declaration time 1).
1
Coast to stop.
2
Fast-stop - according to C1-09.
3
Alarm flashes, operation continues
(factory default).