YASKAWA
TOEPC71061782C GA800 Drive Installation & Primary Operation
69
*3
The control circuit is a Safety Extra-Low Voltage circuit. Separate this circuit from other circuits with reinforced insulation. Make sure
that the Safety Extra-Low Voltage circuit is connected as specified.
*4
Reinforced insulation separates the output terminals from other circuits. Users can also connect circuits that are not Safety Extra-Low
Voltage circuits if the drive output is 250 Vac 1 A maximum or 30 Vdc 1 A maximum.
■
Main Circuit Wire Gauges and Tightening Torques
WARNING
Fire Hazard. Use terminals - and +3 for the braking resistor connections. If you connect a braking resistor to the
incorrect terminals, it can cause damage to the drive and braking circuit and serious injury or death.
Note:
•
The recommended wire gauges are based on drive continuous current ratings with 75 °C (167 °F) 600 V class 2 heat-resistant indoor PVC
wire. Assume these conditions:
–
Ambient temperature: 40 °C (104 °F) maximum
–
Wiring distance: 100 m (328 ft) maximum
–
Normal Duty rated current value
•
Refer to the instruction manual for each device for recommended wire gauges to connect peripheral devices or options to terminals - and
+3. Contact Yaskawa or your nearest sales representative if the recommended wire gauges for the peripheral devices or options are out of
the range of the applicable gauges for the drive.
6-Phase/12-Pulse 400 V Class
Model
Terminal
Recomm. Gauge
mm
2
Applicable Gauge
mm
2
Wire Stripping
Length
mm
Terminal Screw
Size and Shape
Tightening Torque
N
∙
m (lbf
∙
in)
T103
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
16 × 1 × 2
10 - 25
14
M5
2.3 - 3
(20 - 27)
U/T1, V/T2, W/T3
35
25 - 70
24
M8
15.3
(135)
-, +3
25
1.5 - 50
18
M6
3.1 - 3.8
(28 - 33)
16
16 - 25
-
M6
5.4 - 6
(47.8 - 53.1)
T140
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
25 × 1 × 2
10 - 50
18
M6
3.1 - 3.8
(28 - 33)
U/T1, V/T2, W/T3
50
35 - 95
33
M8
20
(175)
-, +3
50
25 - 70
24
M8
15.3
(135)
25
25 - 50
-
M8
9 - 11
(79.7 - 97.4)
T168
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
25 × 1 × 2
16 - 50
18
M6
3.1 - 3.8
(28 - 33)
U/T1, V/T2, W/T3
70
50 - 95
33
M8
20
(175)
-, +3
50
25 - 70
24
M8
15.3
(135)
35
25 - 50
-
M8
9 - 11
(79.7 - 97.4)
T208
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
35 × 1 × 2
25 - 95
-
M10
20
(177)
U/T1, V/T2, W/T3
50 × 2
70 - 95
-
M10
20
(177)
-, +3
35 × 2
22 - 70
-
M10
20
(177)
50
50 - 240
-
M10
18 - 23
(159 - 204)