Installation and Operation Guide SOLECTRIA PVI 25TL-480-R
DOCR-071030-A (11/17/2020)
Page 70 of 101
Table 5-7 Enable / Disable Parameters with Lower Limit, Default and Upper Limit Settings (IEEE 1547-2018 and Rule 21)
Parameter name
Description
Setup range
(lower limit,
default & upper
limit) IEEE1547
Setup range
(lower limit,
default & upper
limit) Rule-21
CtrParaGroup
The enabled control parameters
group.
0:Article 5 groups, control
parameter setting of inverter loop
1:Article 1 groups, control
parameter setting of inverter loop
2:Article 2 groups, control
parameter setting of inverter loop
3:Article 3 groups, control
parameter setting of inverter loop
4:Article 4 groups, control
parameter setting of inverter loop
{0, 4, 4}
{0, 4, 4}
ReactivePwModeSelect
The control mode of reactive power
0: Disable dispatch mode.
1: Remote dispatch mode.
2: Local control ,by Q
3: Local control ,by PF
4: PF(P)curve
5: Q(U) curve
(Association register address=
0x2200. 0x250F.0x2707. 0x2709)
6:Q(P)Curve
{Disable, Disable,
Remote
,
Q,PF,PF(P),Q(u),
Q(P)}
{Disable, Q(u),
Remote
,
Q,PF,PF(P),Q(u) ,
Q(P)}
ActivePwModeSelect
The control mode of active power
0: Disable dispatch mode.
1: Remote dispatch mode.
{Disable, Disable,
Remote,Local}
{Disable, Disable,
Remote,Local}