Save the bulkhead connector cover and screws and attach the cover to the left side of the wire-box after the wire-box is
attached to the inverter enclosure. Covers may be required in the future if an inverter or wire-box is to be removed
during servicing.
Tool required: No.2 Phillips head screwdriver
Secure the Power Head to the Wire-Box
3.2.6.4
Secure the wire-box to the main enclosure by using the M6x18 screws (4pcs) to fasten the wire-box.
Tool required: No. 10 Wrench or No. 3 Phillips head screwdriver, torque value of 4 Nm (35.4in-lbs) not sure which
tool.
WARNING
Incorrect Torque Leads to Improper Bonding:
Ensure the M6x18 screws (4 pcs) for Section 3.2.6.4 are properly torqued
and 4 Nm (35.4 in-lbs). This connection provides an electrical grounding bond of the Wire-Box to the upper/main
enclosures.
Figure 3-8 Securing Wire-Box to Power Head
Attach Enclosures to Mounting Bracket
3.2.6.5
Attach the main enclosure and the Wire-Box to the mounting bracket with
M6x18 screws
(6 pcs) as shown in Figure 3-8.