Installation and Operation Guide SOLECTRIA PVI 25TL-480-R
DOCR-071030-A (11/17/2020)
Page 46 of 101
Figure 3-30 Third-Party Data Logger Connection Point on the Ethernet Network Card
Figure 3-31 PVI 25TL-480-R Inverters in a RS-485 Daisy Chain to Third-Party DAS
When connected to an external DAS, Yaskawa Solectria Solar PVI 25TL-480-R inverters support up to 32
inverters/devices on the RS-485 daisy chain. The Inverter Modbus IDs are configurable from 1 to 128.
Yaskawa Solectria Solar recommends limiting the RS-485 daisy chain to a maximum length of 3000 ft. (914m).
Care must be taken when daisy chaining the inverters, utilizing a shielded twisted pair cable such as Belden 9841
or Southwire 58165802.