Table 5-2 Active Power Derating Setup Ranges with Lower Limit, Default, and Upper Limit for IEEE 1547-2018 and CA Rule 21
PARAMETER
NAME
DESCRIPTION
SETUP RANGE
(LOWER LIMIT,
DEFAULT & UPPER
LIMIT) IEEE1547-
2018
SETUP RANGE
(LOWER LIMIT,
DEFAULT & UPPER
LIMIT) RULE21
OvrFrqMin
The trigger frequency of
OverFrequency derating
{60, 60.04,72}
{60, 60.04 ,72}
OvrFrqMax
The end frequency or Rate of
Overfrequency derating (Depends on
the specific standard)
{60,62.532,72}
{60, 62.034 ,72}
OvrFrqSlop
The Rate of Overfrequency derating.
{0.01%,30%,100%}
{0.01%,30%,100%}
RecoveryFrq
The recovery frequency of
OverFrequency derating
{58.8, 59.964 ,66}
{58.8, 59.964 ,66}
OvrFrqRecoveryT
The recovery time of OverFrequency
derating
{0,60,1200}
{0,60,1200}
VirtualDamping
Resonance damping coefficient
{0,0,5}
{0,0,5}
OperationOverVol Operating overvoltage protection value {100%,120%,135%} {100%,120%,135%}
VwCurveV1
Grid overvoltage derating starting
voltage V1
{100%, 106%,110%} {100%, 106%,110%}
VwCurveP1
Grid overvoltage derating starting
power P1
{0%,100%,100%}
{0%,100%,100%}
VwCurveV2
Grid overvoltage derating end voltage
V2
{100%,110%,135%} {100%,110%,135%}
VwCurveP2
Grid overvoltage derating end power
P2
{0%, 0%,100%}
{0%, 0%,100%}
OpenLoopRespT
Open loop response time
{0.5,10,90}
{0.5,10,90}
ReactivePowerDerating
5.2.2.2.3
The “ReactivePowerDerating” submenu is used to set the Grid reactive power derating parameters including PF
parameters and Q parameters, etc. The parameters are shown in Figure 5-10.
Note: The PF and Q value can be adjusted by remote software if the “Remote” is selected.