4 Option Components
YASKAWA
TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
15
Table 3 Option LED States
Name
Indication
Operating Status
Remarks
Color
Status
MS
(visible
through
drive cover)
–
OFF
Power supply OFF
Power is not being supplied to the
drive.
Green ON
Option
operating
The option is operating normally and
initialization is complete.
Green
Flashing (1)
Diagnostics
Diagnostic data available.
Green
Flashing (2)
Configuration tool
Identified by a configuration tool.
Red ON
Default MAC or fatal error
occurred.
Default MAC address has been
programmed or the option has
detected an unrecoverable error.
Red
Flashing (1)
Configuration error (non-fatal)
Configuration error.
Red
Flashing (2)
No IP (non-fatal)
No IP address assigned.
Red
Flashing (3)
No station name (non-fatal)
No station name assigned.
Red
Flashing (4)
Init failure (non-fatal)
Failed to initialize module.
Green/
Red
Flashing
Option self-test
The option is in self-test mode.
NS
(visible
through
drive cover)
–
OFF
Offline or Power supply OFF
–
Green ON
Connected
Connection established with I/O
controller and in RUN mode.
Green
Flashing
Connected and stopped
Connection established with I/O
controller and in STOP mode.
Red
ON
BUS fault
Unrecoverable BUS fault.
Red Flashing
(1)
Lost
communication
Host communication is temporarily
lost.
Red Flashing
(2)
Lost
link
No
link detected to network.
10/100
(visible at
RJ45 cable
ports)
Yellow
OFF
10 Mbps is established
–
Yellow
ON
100 Mbps is established
–
LINK/ACT
(visible at
RJ45 cable
ports)
Green
OFF
Link is not established
–
Green
ON
Link is established
–
Green
Flashing
Link is established and there is
network activity
–