6 Procedure A
YASKAWA
TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
31
16.
Connect the ground wire at the option ground terminal FE. Tighten the screw to 0.5
~ 0.6 Nm or (4.4 ~ 5.3 in lbs) using an M3 Phillips screwdriver.
Figure 23
Figure 23 Connect the Ground Wire to the Option
17.
To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair
Cat5e cable(s) into the modular connector ports.
.
NOTICE:
Do not connect or disconnect the communication cable while the drive is powered up or while the
drive is in operation. Failure to comply may cause a static discharge, which will cause the option card to stop
working properly. Cycle power on the drive and option card to attempt to reestablish functionality.
Figure 24
Figure 24 CN1 RJ45 CAT5e Communication Cable Ports
Option ground
terminal FE
Ground wire to
drive ground terminal
screw
RJ45 8-pin Shielded Twisted Pair
Cat5e cable(s)