![YASKAWA iQpump Series Скачать руководство пользователя страница 97](http://html1.mh-extra.com/html/yaskawa/iqpump-series/iqpump-series_programming-manual_3564785097.webp)
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
97
Figure 1.82
Figure 87 Motor Overload Protection Time based on Output frequency and Load
■
L1-03 Motor Overheat Alarm Operation Selection
■
L1-04 Motor Overheat Fault Operation Selection
■
L1-05 Motor Temperature Input Filter Time
Setting Range:
0.00 to 10.00 sec
Factory Default: 0.20 sec
The iQpump drive can be programmed to accept a PTC (Positive Temperature Coefficient) Thermistor input for monitoring motor
temperature. By setting parameter H3-09 = “E: Motor Temperature,” and attaching the PTC thermistor per the figure below, the iQpump
drive can react to the increasing motor winding temperature with both an alarm (L1-03) and a fault (L1-04).
Setting
Description
0
Ramp to Stop
1
Coast to Stop
2
Fast-Stop
3
Alarm Only (
factory default
)
Setting
Description
0
Ramp to Stop
1
Coast to Stop (
factory default
)
2
Fast-Stop
125%
4
2
Time
(M
inut
es
)
Output Current
(Percent of motor FLA)
E2-01 200%
6
8
10
60Hz
10Hz
175%
150%
Содержание iQpump Series
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...