![YASKAWA iQpump Series Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/yaskawa/iqpump-series/iqpump-series_programming-manual_3564785128.webp)
128
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
Figure 1.98
Figure 103
Loss of Prime (LOP)
■
P1-15 Low Water Input
The iQpump drive can be configured to detect a low water level condition. To activate the low water level detection requires one of the
multi-function digital inputs to be programmed for low water level (H1-xx = 85). The multi-function digital input can be configured to
accept a normally closed or normally open contact by programming the Low Water Input (P1-15).
This function is only active during operation in the Auto Mode.
Important: Refer to H1-xx = 85 on page
for further description of the low water level function.
Setting
Description
0
Closed at Low Water (
factory default
)
1
Open at Low Water
TIME
Loss of Prime
(LOP) Fault
Loss of Prime
P1-12
P1-14
Fmax
- 1 Hz
OUTPUT
CURRENT
OUTPUT
FREQUENCY
Содержание iQpump Series
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...