Figure 1.5
Figure 5 Connection Diagram of PC or PLC
If you want the iQpump drive to receive the “Auto Setpoint” for a network communication option card:
Set b1-01= “3: Option
PCB,” and plug a network option board (p/n SI-J) into the 2CN port on the iQpump drive Control PCB. Consult the manual supplied with
the option board for instructions on integrating the iQpump drive into the network system.
The iQpump drive can support the following network communication options. Refer to the appropriate Installation Guide (IG) and
Technical Manual (TM) for further details. These network communications documents can be located at
http://iQpump.yaskawa.com
.
Important:
If b1-01 = “3: Option PCB” but a network card is not installed in 2CN, an OPE05 Operator Programming Error will be
displayed on the digital operator and the iQpump drive will not run.
■
b1-02 Run Source
■
Start/Stop from Keypad (Parameter b1-02 = 0)
The iQpump drive comes factory programmed for Start and Stop from the Keypad.
The iQpump drive can be programmed to receiver a Run command from four different inputs: digital operator, terminals, serial
communications, or an option PCB.
If the Run command input is determined by the digital operator: Set b1-02 = “0:
Operator,” and the hand key will be used to provide
the Run command to the iQpump drive.
If the Run command input is determined by the external terminals:
Set b1-02 = “1: Terminals” and initiate an external Run
command by a contact closure between terminals S1 and SN. Refer to
for the connection diagram of the external Run command.
Note:
To use the external terminals requires the iQpump drive to be set to “Auto” mode by pressing the Auto key.
• Profibus DP Option Card CM061
Manual: IG.AFD.12
• DeviceNet Option Card CM05X
Manual: IG.AFD.14
• Modbus Plus Option Card CM071
Manual: IG.AFD.17
• Modbus TCP/IP Option Card CM090
Manual: IG.AFD.25
• EtherNet/IP Option Card CM092
Manual: IG.AFD.26
Setting
Description
0
Operator (
factory default
)
1
Terminals
2
Serial Com
3
Option PCB
Содержание iQpump Series
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...