Fault Trace List
Table 3 Fault Trace List
Parameter No.
Modbus
Address
Fault Trace
U2-01
0080H
Current Fault
Current Fault
U2-02
0081H
Previous Fault
Last Fault
U2-03
0082H
Frequency Reference at Most Recent Fault
Frequency Ref
U2-04
0083H
Output Frequency at Most Recent Fault
Output Freq
U2-05
0084H
Output Current at Most Recent Fault
Output Current
U2-07
0086H
Output Voltage at Most Recent Fault
Output Voltage
U2-08
0087H
DC Bus Voltage at Most Recent Fault
DC Bus Voltage
U2-09
0088H
Output Power at Most Recent Fault
Output kWatts
U2-11
008AH
Input Terminal Status at Most Recent Fault. The format is the same as for U1-10.
Input Term Sts
U2-12
008BH
Output Terminal Status at Most Recent Fault. The format is the same as for U1-11.
Output Term Sts
U2-13
008CH
Drive Operation Status at Most Recent Fault. The format is the same as for U1-12.
Inverter Status
U2-14
008DH
Cumulative Operation Time at Most Recent Fault
Elapsed time
Note:
Fault trace is not executed at CPF00, CPF01, CPF03, UVI and UV2.
Содержание iQpump Series
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...