YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
87
◆
Write In Several Holding Registers (10H)
Write the specified data to the desired slave indicating the desired starting register. The written data must be consecutive, starting from
the specified address in the command message: High Byte (8 bits), then Low Byte 8 bits, in sequential storage register order.
The following table shows an example of a message when a forward Run command has been set at a speed command of 60.0 Hz in the
slave 1 iQpump drive by the PLC.
Figure 84 Function Code 08H Message Example
Important:
Set the number of bytes as quantity of specified registers x 2. Handle response messages in the same way.
Command Message
Response Message
(During Normal Operation)
Response Message
(During Error)
Slave Address
01H
Slave Address
01H
Slave Address
01H
Function Code
10H
Function Code
10H
Function Code
90H
Start
Register
High
Byte
00H
Start
Register
High
Byte
00H
Error code
02H
Low
Byte
01H
Low
Byte
01H
CRC-16
High
Byte
CDH
No. of
Registers
High
Byte
00H
No. of
Registers
High
Byte
00H
Low
Byte
C1H
Low
Byte
02H
Low
Byte
02H
No. of Bytes*
04H
CRC-16
High
Byte
10H
First
2 Bytes
of data
High
Byte
00H
Low
Byte
08H
Low
Byte
01H
Second
2 Bytes
of data
High
Byte
02H
* No. of bytes = 2 x (# of Registers)
Low
Byte
58H
CRC-16
High
Byte
63H
Low
Byte
39H
Содержание iQpump Series
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...